Model number identification, Theory of operation – Precision Control Systems 1025 User Manual

Page 11

Advertising
background image

MODEL 1022 & 1025

8

05/10/2007

MODEL NUMBER IDENTIFICATION

102X-VV-AA [-SCXXX] [-MOXX]

X = 2 for 1022,

5 for 1025

1022 (0/5Vdc, 0/10Vdc or POT control)

1025 (4/20mA input)

VV = Rated voltage:

12 = 120Vac

24 = 240Vac

48 = 480Vac

57 = 570Vac

AA = Rated amps:

10, 20, 30, 40, or 70 amps

Note:

The addition of

"-SCXXX" implies that the controller has been modified to have a different input command. For example,

a "-SC1/5Vdc" implies the controller has been modified to operate with a 1/5Vdc control signal.

The addition of "-MOXX" implies a special mounting or assembly of the controller.

THEORY OF OPERATION

The model 1022 and 1025 are phase-angle controllers, therefore, the load voltage is controlled by turning the appropriate

SCR on for a portion of each electrical half cycle as shown in Figure 6. The waveform shown as E

L

represents the “ON”

time of the SCRs in each half cycle and therefore represents the voltage waveform applied to the load. As the load

voltage is increased the SCRs are turned ON earlier in the cycle. As the load voltage is decreased the SCRs are turned

on later in cycle. The load voltage can be varied with infinite resolution from 0 to 100 percent of the line voltage. Circuit

tolerances may limit the maximum load voltage to about 97% of the supply voltage.

Is

I

E

Es

L

L

L

O

A

D

Figure 6. Phase angle control at 50% power.

Advertising
This manual is related to the following products: