Rola-Chem RC554X ORP Digital Controller User Manual

Page 6

Advertising
background image

Rola-Chem Digital Controller PN 554237 02/17/2014 Page: 6 of 12

3.2 Specifications

Display:

0 to 995 mV

Control:

400 to 900 mV

Factory default:

650 mV

Input Power
120 Volts AC, 50/60 HZ, 3 wire grounded power cord.
GFCI source required

Output Power

120 Volts AC, 50/60 HZ, 5 amps (fused)

Two 3-wire grounded power receptacles

Terminal strip for hardwire applications.


Displays:

ORP reading

-red digital LED

Flow/Power indicator

-green LED

Auto (operating mode) indicator -red LED
Alert indicator -red LED
Feed indicator -green LED


Note: lamps flash during feeding and are on constant during delay time of feed cycle.

O

perating Temperature: 40 to 120° F


Features and Options
+ORP setting

+ ORP feed/delay time + alert (high & low)

+ Flow switch input

+ Feed time out

+ fused output

3.3 Description of Controls


Modes: The controller has two modes of operation:

• ON/OFF/Set mode
• AUTO mode- operating

To move from one mode to another simply press the MODE button.

On/off /Set mode:

• To turn the controller “on”, press the MODE button.
• To turn the controller “OFF” press MODE so the AUTO light is off and hold the

MODE button for two seconds until the ORP displays read “OFF”.

Release the MODE button, the controller turns off and the display goes blank.