3.3 Description of Controls

1. WATER FLOW LAMP

Illuminates bright when water flow is
indicated. Also indicates that power
is on.


2. pH/ORP ALERT LAMPS

Illuminates red when the Hi or Low
Alert levels are reached.


3. CHEMICAL FEED LAMPS
pH FEED lamp flashes while feeding
chemical and illuminates steady
during feed delay.
ORP1 & ORP2 FEED lamp flashes
while feeding chemical and
illuminates steady during feed delay.

4. pH/ORP DIGITAL DISPLAYS

Monitors pH and ORP and displays
programmed set points.

5. pH STANDBY LAMP AND PROGRAMMING BUTTONS

When pH standby lamp is illuminated the six set buttons are enabled.


6. MODE BUTTON AND AUTOMATIC LAMP
Press Mode button to pH or OPR and then hold for 2 seconds for OFF.

Press and release Mode button to step from pH standby to ORP1 to ORP2 standby.
Press again to return to AUTOMATIC mode.


7. ORP STANDBY AND PROGRAMMING BUTTONS
When ORP1 lamp is illuminated the five SET buttons are enabled.
When ORP2 lamp is illuminated the three SET buttons are enabled.

8. pH/ORP SENSOR CONNECTORS- BNC type


Modes: The controller has five modes of operation:

• ON/OFF mode.
• AUTO mode- operating
• pH - setting mode
• ORP1- setting mode
• OPR2 - setting mode

To move from one mode to another simply press the MODE button.
The illuminated lamp indicates the current mode.

pH ORP FLOW SWITCH

pH OUTPUT

ORP1 OUTPUT ORP2 OUTPUT

POWER