Designed to be used with a variety of SeaMetrics
meters, the FS20 signals when flow reaches critical
setpoints. Two setpoints are provided, a low and a high
setting. When flow falls below the low or rises above
the high, SPDT relay contacts close to actuate what-
ever alarms or controls are connected to them. Set-
ting is by means of DIP switches, and setpoints are in
pulses per minute. Output lights give visual indication
that flow limit has been reached.

Specifications

Power

115 VAC

Enclosure

NEMA 4x, 5" x 7" polycar-
bonate

Relays

SPST

Relay Rating

5 A resistive at 115 VAC
5 A at 24 VDC

Setpoint Range

1 - 33,000 pulses/
minute

Setpoint Hysteresis

6%

Sensor Power

25 mA at 12 VDC
nominal

Features

Mounting. To gain access to the mounting screw holes,
remove the front clear cover. Mounting screw holes
are at the four corners, under the cover screws. Mark
the centers of these holes, using the box or the en-
closed template, and drill. Finally, insert screws through
the corner holes and tighten.

Terminal Access. Terminals are on the back side of
the printed circuit board. Remove the front clear cover,
then remove the four front plate screws. Turn the printed
circuit board over to reach the terminals.

Connect Flow Meter. Bring the flow meter input cable
into the unit through the appropraite strain relief, then
connect following the Connections diagram. Either two-
wire (dry contact) or three-wire (solid state) flow meter
sensors can be used.

Connect Alarm Relay(s). Bring alarm output cable(s)
into the unit through the appropriate strain reliefs and
connect to relay outputs, as shown in the Connections
diagram. Note that depending on setting, relays may
energize when the unit is first powered up. If this
presents a hazard, disconnect any devices on the
other end of the cable(s) until settings have been
made and tested.

General Information

Installation

Input Indicator

High Flow Setting

Low Flow Setting

Power switch
and indicator

Cover screws
and box mounting
screw holes

strain relief

Power input cord
(6’ length)

Low flow
relay output

Internal 10 Amp
replaceable fuse

Output Indicators

OFF

ON

MANUAL

MANUAL

INC. KENT, WA

INPUT

LOW FLOW

HIGH FLOW

FS20

FLOW SWITCH

OFF

ON

OFF

ON

16384

16384

32768

32768

8192

8192

4096

4096

2048

2048

1024

1024

512

512

256

256

32

32

64

64

128

128

16

16

8

8

4

4

2

2

1

1

Setting equals
the sum of
the switches
turned "ON".

Setting equals
the sum of
the switches
turned "ON".

L

O

W

F
L

O

W

H

I

G
H

F
L

O

W

High flow
relay output

Meter input

DIS

CON

TIN

UED

Advertising