Spectrex 20/20SI Triple IR (IR3) Flame Detector User Manual

Page 20

Advertising
background image

Spectrex Inc. - SharpEye

TM

IR3 Flame Detector Manual – TM 20/20I, Rev. (6) August 2004

12

4.3.1 Function switch (SW1):
The user can select the desired mode of operation by means of this switch
according to table 6:

Table 6: Function Switch SW1

SW.

ON Position

OFF Position

1

Alarm latching - enabled

Alarm latching – disabled (default)

2

Accessory relay activated at warning
level

Accessory relay activated at
detection level (together with Alarm
relay) - (default)

3

Automatic & manual BIT (default)

Manual BIT only

4

Successful manual BIT activates the
Alarm relay and the 4-20mA output
turns to 15mA for approximately 3
seconds (default)

Successful manual BIT does not
activate the Alarm relay.

5

Successful manual BIT activates the
accessory relay and the 4-20mA
output turns to 10mA for
approximately 3 seconds (default)

Successful manual BIT does not
activate the Accessory relay.

6*

Sensitivity range – see table 7 below
(default)

Sensitivity range - see table 7

7*

Sensitivity range - see table 7 below Sensitivity range - see table 7

(default)

8

Accessory relay used as End Of
Line.

Accessory relay operates in
accordance with the settings of
SW1(default)

* See Table 7 for sensitivity range setting.

Table 7: Sensitivity range

Sensitivity

Range

SW1-7

SW1-6

1 (lowest)

50 ft (15m)

OFF

OFF

2 100

ft

(30m)

OFF

ON

3 150ft

(45m)

ON

OFF

4 (highest)

200ft (60m)

ON

ON

Advertising