Ls le, Consult factory, Initial startup and operation – Warren Controls AmurAct Actuator Linkage and Motor User Manual

Page 9

Advertising
background image

9

AmurAct

IOM_AA_RevH_0413

INITIAL STARTUP AND OPERATION

1.

After verifying that line isolation valves are shut, that wiring

connections and motor switches are properly positioned, and Amu-

rAct linkage safety covers are in place, apply power to the motor.

Observe

that the led light remains lit for 30 seconds. After the led goes off, in-

dicating that the Enerdrive capacitors are sufficiently charged, press

and release the small RESET pushbutton beside the led (see page

6 for location). The motor and valve will run through a slow-speed

calibration cycle, and then stop.

Initiate this

Autostroke calibration cycle each time AmurAct is

placed into service following an intentional shutdown, adjustment

or maintenance. It apportions the input signal over the actual range

of valve stem movement for maximum accuracy of control, and pro-

vides “soft stops” at both ends of travel to reduce gear impact and

extend motor life. Failure to do so can result in inaccuracy of control
and premature failure of the motor.

The 30-second pause occurs each time power is applied to the mo-

tor, and allows the motor to recall its internal settings. No operator

action is needed to return to fully automatic operation following a

power outage. The Enerdrive fail-safe energy supply is fully restored
within one minute after power is restored.

2.

Apply a control signal and observe that the control valve re-

sponds correctly by opening with an increasing signal and closing

with a decreasing signal (This is with the default setting). Install the

motor cover.

3.

Fail-safe operation can be tested at any time by interrupting

power to the motor. Recall that there is up to a 30-second delay

after power is restored.

4.

With power and control signal applied, slowly and carefully

open the isolation valves. Observe that the controller and control

valve have control of the process before leaving the area.

Ls

Le

TO RE-ORIENT

ThE AMURACT

ON ThE VALVE

CONSULT
FACTORY

If it is necessary to

re-position AmurAct

on the valve call the

factory at

610-317-0800

for procedural

assistance.

Failure to do so will

void the warranty

coverage.

STANDARD LINKAGE

EXTENDED LINKAGE

Advertising