Adjustment ranges, Default values/settings – West Control Solutions 2300 User Manual

Page 5

Advertising
background image

2.1

Adjustment Ranges

2.2

Default Values/Settings

OM076

Page 5

June 1997

1/32-DIN Temperature Controller

Operator's Manual

Parameter

Setpoint(s)
Proportional Band
Reset
Rate
Bias (Manual Reset)
ON/OFF Hysteresis
Alarm (1 & 2) level

Input Filter Time Constant
Input Offset
Output Cycle Time
Setpoint Lock
Alarm Value Display Enable/Disable

Default Value/Setting

Input Range Min.

10.0%

5 minutes

1 minute 15 seconds

25%

0.5% of input span

Alarm 1 Process High: Input Range Max.

Alarm 2 Process Low: Input Range Min.

2 seconds

0

16 seconds

(adjustment enabled)

(enabled)

Parameter

Setpoint(s)

Proportional Band
Reset

Rate

Bias
(Manual Reset)
ON/OFF Hysteresis
Alarm (1 & 2) level

Input Filter Time Constant
Input Offset

Output Cycle Time
Setpoint Lock

Alarm Value Display
Enable/Disable

Adjustment Range

Input Range Min. to Input Range Max.

NOTE: Negative values limited by display to –1999

0.5% to 999.9% (0.1% increments)

1 sec. to 99 min. 59 sec.

and OFF (>99min. 59 secs.)

0 (OFF) to 99 min. 59 sec.

0% to 100%

0.1% to 10.0% of input span

Process High: Input Range Min. to Input Range Max.

Process Low: Input Range Min. to Input Range Max.

Deviation (High or Low): –(input span) to +(input span)

Band: 1 LSD to Input Span

NOTE: Negative values limited by display to –1999

0sec. to 100sec.

±

input span

NOTE: Negative values limited by display to –1999

0.5 (SSR only), 1, 2, 4, 8, 16, 32, 64, 128, 256 & 512 sec.

adjustment enabled in Normal Operation
adjustment disabled in Normal Operation
display/adjustment enabled in Normal Operation
display/adjustment disabled in Normal Operation