West Control Solutions CALogix User Manual

Page 24

Advertising
background image

The current proportional output of SP3 shown as %.


Manual Power

Off

Off, 0 to 100, step 1

Manual power overrides PID calculated power output. The proportional output for SP3 will remain constant at the entered value. To return to
PID control set manual power to 0.


Display Alarm

No

No,

Yes

When set to yes, alarm symbol is shown on controller image within CALogix-sw when an alarm output is switched.


Reset Latched Alarm

No

No,

Yes

Used to clear a latched alarm output on SP3, once the alarm condition has cleared. Set value to yes to clear.


Module * - Programmer

Default

Options


Program number

0

1 to 31

Select programmer profile to run. See section on programmer

Run mode

Off

Hold,

Run,

Off

Program run mode. See section on programmer

Page 24 of 44