18

9499 040 55811

Multiple transmitter and temperature controller KS 816

Address and Baudrate for the COM2 interface can be adjusted via hardware or
software for each KS 800.

Via hardware, the address is adjustable within ”01” and ”99”. In position ”00”, the
address stored in EEPROM which can be changed via software will be used when
switching on. Priority is given to the address adjusted via switch position. This
address cannot be changed via software.

The same applies to the Baudrate: in Position ”0”, the EEPROM Baudrate is effec-
tive at first. This address can be changed via software. The digits on the switch cor-
respond to the values used for determination of the Baudrate during configuration in
C902.

Switch position

RS485

CANbus

0

from EEPROM or via software

from EEPROM or via software

1

2400 Bd

20 kBd

2

4800 Bd

125 kBd

3

9600 Bd

500 kBd

4

19200 Bd

1 Mbd

5

invalid setting

10 kBd

6

invalid setting

50 kBd

7

invalid setting

250 kBd

8

invalid setting

800 kBd

9

invalid setting

invalid setting

As the baudrate is adjusted automatically with the PROFIBUS DP-version, manual
adjustment is omitted.