Danger – Advanced Protection XCS User Manual

Page 4

Advertising
background image

4

SPDs on Ungrounded Systems

Caution – Ungrounded systems are inherently

unstable and can produce excessively high line-

to-ground voltages during certain fault conditions.

During these fault conditions, any electrical equipment

including an SPD, may be subjected to voltages

which exceed their designed ratings. This information

is being provided to the user so that an informed

decision can be made before installing any electrical

equipment on an ungrounded power system.

Connecting Optional Form C Dry Contact &

Audible Alarm

Three (3) 3’ (~1m) 18 AWG wires are included

through the nipple with this option. (These are

smaller than the 10 AWG SPD conductors.) Gray

is Common, Blue is Normally Open and Red is

Normally Closed. (We generally recommend the

Normally Closed configuration because it detects

disconnected or failed wiring whereas Normally

Open does not.)

If the Dry Contacts are not utilized, insulate lead

ends, coil and secure. Audible Alarm will still

function correctly.

The contact is rated 250V, 5A. Higher energy

applications require supplemental relaying. This

option monitors suppression element condition

and is not intended for use as phase loss or phase

detection monitoring.

Remote Indication Option

This option includes a supplemental diagnostic LED

that can be mounted in a conspicuous location. For

example, assume that the SPD is mounted such

that it is not readily visible. A Remote Indicator can

provide visual indication of correct operation.

Operation is straightforward: green LED On = SPD

is OK. If the LED is out, the SPD has failed, power is

not present, or one of more phases are not energized.

The green LED assembly includes two pre-attached

wires and two butt-splice connectors. The SPD

includes two yellow 18 AWG wires, pre-wired

through the SPD’s nipple mounting connection.

Pre-plan the installation per normal Installation

Instructions. Mount the LED assembly in an

appropriate conspicuous location. Connect the LED

wires to the yellow SPD wires with the provided butt-

splice connectors. These are not polarity sensitive.

Test by energizing and deenergizing SPD.

NORMAL OPERATION

Green LED Indicators

Each phase’s LED Indicator illuminates when the

SPD is energized and operating correctly. Every

suppression element is monitored and connected

by logic to the LED. Should any suppression

element fail, the green LED will extinguish.

Form C Dry Contact and Audible Alarm Option

Similar to the green LEDs above, the Dry Contact

will change state and the Audible Alarm will sound

upon suppression element failure. The Audible

Alarm may be silenced by removing power to

the SPD.

MAINTENANCE

SPDs require minimal maintenance. We recommend

periodic inspection of diagnostic indicators to ensure

proper operation. We also recommend keeping the

SPD clean as appropriate.

Troubleshooting & Service

Please contact us for any service related issues.

We want to take care of any problems.

Quality SPDs withstand severe duty and attempt to

protect their load until failure. There are electrical

anomalies that SPDs cannot protect against. These

are generally Sustained Overvoltages also known

as Temporary Overvoltages (TOVs). In this context,

Sustained Overvoltages may be only a few cycles.

Failed SPDs tend to be symptoms, not root causes.

We suggest treating a failed SPD as a ‘canary in the

coal mine’ as there may be larger issues at play. As

a generalization, the single largest ‘killer’ of SPDs is

reference to ground issues. If the SPD shows problems

on startup, there is reasonable chance of bonding/

grounding/misapplication issue. This permanently

damages the unit. If not corrected, it will happen again.

There are no user serviceable parts inside. We

strongly recommend against disassembly.

Units may be returned to the factory for factory service,

qualification and return. Please contact factory at

(800) 237-4567 for assistance.

Dry Contact

Leads

(18 AWG)

Power Leads

(10AWG)

Blue

Gray

Red

Figure 5

Normally Closed

(suggested):

Use Gray

and Red

Normally Open:

Use Gray and Blue

LEADS

Hazardous voltage.

Will cause death or serious injury.

Keep Out.

Qualified personnel only.

Disconnect and lock off all power before

working on this equipment.

V

DANGER

Advertising