Installation Data

WATER SYSTEM

Chilled water pipework and ancillary components must be installed in accordance with:

National and Local Water supply company standards

The manufacturer's instructions are followed when fitting ancillary components

The system liquid is treated to prevent corrosion and algae forming

In ambients of 0°C and below, where static water can be expected, or when water
supply temperatures of +5°C or below is required, the necessary concentration of
Glycol or use of an electrical trace heater must be included

The schematic is referred to as a guide to ancillary recommendations

CAUTION

The unit water connections are NOT designed to support external pipework,
pipework MUST be supported separately.

STANDARD RECOMMENDED INSTALLATION
(Parts Supplied by Others)

GENERAL

The following diagram illustrates the minimum component installation requirements. A
wide range of optional extras are available to suit various applications, please refer to

General Description

, on page 11 for details.

CAUTION

The following installation recommendations should be adhered to. Failure to do
this may invalidate the chiller warranty.




P

T

(10)

(9)

(4)

(7)

(3)

(2)

(1)

(6)

(8)

(11)

(12)

T

P

(5)

(1) Flexible connections
(2) Pressure gauges
(3) Temperature gauges
(4) Binder points
(5) De-aerator (optional extra)
(6) Auto air vent (at highest point)

(7) Strainer (optional extra)
(8) Flow switch
(9) Shut off valves
(10) Bypass circuit (for flushing)
(11) Pump
(12) Pump strainer

CAUTION

Full design water flow MUST be maintained at all times. Variable water volume is
NOT recommended and will invalidate warranty

CAUTION

The correct operation of the flow proving device is critical if the chiller warranty is
to be valid.

CAUTION

Following components are fitted within the chiller unit as standard:

Temperature Sensors

Drain Point

Auto Air Vent