Monitoring, Logicool ™ chillers, Controls – Airedale LogiCool FreeCool 40kW User Manual

Page 18

Advertising
background image

LOGICOOL

Chillers

18

Chillers

Technical Manual : 6521355 V1.8.0 07/2014

Controls

MONITORING

The microprocessor also monitors and displays the following measured parameters:

Supply Water Temperature

Return Water Temperature

Evaporator Inlet water temperature

Ambient Air Temperature

Suction Pressure

Liquid Pressure

Evaporator Waterside Differential Pressure

Evaporator Waterside Flow Rate (calculated)

ALARM HANDLING

The following conditions will be detected, triggering a visual alarm:

Low Supply Temperature

Mains Phase Failure / Phase Rotation

Emergency Stop (Option)

Water Flow

Pump(s) status

Individual Compressor Trip

Low Suction Pressure

High Liquid Pressure

Low Pressure Switch

Individual Compressor Overload

Isolator Status

Individual High Compressor Discharge Temperature

Volt Free Contact Non-Critical Alarm Indication

Volt Free Contact Critical Alarm Indication