Chillers optichill freecool, Chillers, Mechanical data – regular quiet continued – Airedale OptiChill FreeCool 500kW - 1365kW User Manual

Page 55

Advertising
background image

Chillers

OptiChill Freecool

Chillers

55

Technical Manual :

7197700 v1.2.0 02_2013

Mechanical Data

– Regular Quiet Continued

3

4

Notes

Units

OFC081R16-76MS2

OFC081R16-76ML2

2 Row Free Cool

3 Row Free Cool

2 Row Free Cool

3 Row Free Cool

Cooling Duty - AC Fans

1

kW

806.1

800.5

810.8

805.1

Nom Input -Cooling Only

kW

284.4

287.3

284.8

287.7

EER

2

2.83

2.79

2.85

2.8

ESEER

7

2.9

2.86

2.92

2.87

SEER

7

2.88

2.83

2.89

2.85

Nominal Output - Free Cooling

5

kW

574.2

642.1

575.2

643.4

Ambient when Free Cooling = 100% Nominal DX

6

°C

-1.8

0

-1.9

0

Cooling Duty - EC Fans

1

kW

810.1

806.7

814.9

811.6

Nom Input -Cooling Only

kW

280.5

284

280.9

284.4

EER

2

2.89

2.84

2.9

2.85

ESEER

7

3.2

3.15

3.22

3.16

SEER

7

3.15

3.1

3.17

3.11

Nominal Output - Free Cooling

5

kW

596.9

671.6

598

673.1

Ambient when Free Cooling = 100% Nominal DX

6

°C

-1.3

0.6

-1.3

0.5

Cooling Duty - High Airflow EC Fans

1

kW

809.3

805.9

814.2

810.7

Nom Input -Cooling Only

kW

280.5

284

280.9

284.4

EER

2

2.89

2.84

2.9

2.85

ESEER

7

3.19

3.13

3.2

3.15

SEER

7

3.14

3.08

3.15

3.1

Nominal Output - Free Cooling

5

kW

615.4

694.4

616.6

696

Ambient when Free Cooling = 100% Nominal DX

6

°C

-0.8

1.1

-0.8

1

Capacity Steps

%

20, 30, 40, 55, 65, 80, 90, 100

Dimensions (H x W x L)

mm

2600 x 2200 x 9850

2600 x 2200 x 9850

Machine Weight

kg

11260

11315

11260

11315

Operating Weight

3

kg

12490

12665

12490

12665

Construction Material

Base: Plain Galvanised Steel, Panels: Galvanised Sheet Steel, Epoxy Baked Powder

Paint, Light Grey (RAL 7035)

Evaporator - Type

Shell and Tube

Insulation

Class O / UV Stable

Total Max. Water Flow

l/s

72.8

72.8

58.1

58.1

Total Min. Water Flow

l/s

18.1

18.1

14.4

14.4

Condenser - Type

Rifled Copper Tube / Aluminium Fin

Face Area Total

31.7

31.7

31.7

31.7

Maximum Airflow - High Airflow EC Fans

m³/s

84.9

81.2

84.9

81.2

Maximum Airflow - EC Fans

m³/s

79.2

75.6

79.2

75.6

Maximum Airflow - AC Fans

m³/s

72.5

68.9

72.5

68.9

Condenser Fan & Motor

Sickle Bladed Axial Fan

Quantity

16

16

16

16

Diameter

mm

800

800

800

800

Maximum Speed - High Airflow EC Fans

RPM

1080

1080

1080

1080

Maximum Speed - EC Fans

RPM

980

980

980

980

Maximum Speed - AC Fans

RPM

900

900

900

900

Compressor - Type

Semi-Hermetic Twin Screw Compressor

Quantity

2

2

2

2

Oil Charge Volume (Total)

l

35 + 35

35 + 35

35 + 35

35 + 35

Oil Type

BSE 170 Polyol Ester Oil

Refrigerant - Control

Electronic Expansion Valve

Refrigerant Pre-charged

R134a

Charge (Total) CCT1 + CCT2

kg

156 + 157

156 + 157

156 + 157

156 + 157

Water Connections

Type

Grooved Terminations

Inlet / Outlet - Unit

DN150

DN150

DN150

DN150

Water Drain / Bleed - Evap

inch

0.5

0.5

0.5

0.5

Water System - Volume

l

1228

1346

1228

1346

Minimum System Water Volume

4

l

3547

3657

3559

3669

Max System Operating Pressure

Bar

10

10

10

10

Flow Rate 20% Ethylene Glycol

l/s

43.4

43.1

43.6

43.3

Pressure Drop 20% Ethylene Glycol

kPa

137.6

120.4

175.7

157.8

(1) Based on units performance at 15/10°C return/supply temperatures, 35°C ambient, 20% Ethylene Glycol.
(2) EER = DX Cooling Output / (Compressor Input Power + Fan Input Power)
(3) Based on standard unit without options, operating weight includes refrigerant charge and water volume.
For unit weights with waterside options fitted please refer to Airedale.
(4) For minimum system water volume calculation, refer to Design Features & Information - Minimum System Water Volume Calculations.
(5) Nominal Free Cooling Output at 15/10°C return/supply temperatures, 3°C ambient, 20% Ethylene Glycol.