Ultima compact chillers, Performance data, Not applicable – Airedale Ultima Compact FreeCool 30kW - 450kW User Manual
Page 24
ULTIMA COMPACT
Chillers
24
Chillers
Technical Manual : Part No 6259543 TM E_1.3.0 04/2013
Performance Data
SOUND DATA
Global Chiller Sound Level
Standard - D Models
Sound Measurement
Overall
dB(A)
Frequency (Hz) dB
63
125
250
500
1000
2000
4000
Power
NOT APPLICABLE
Pressure
@ 10m
Power
Pressure
@ 10m
Power
Pressure
@ 10m
Power
Pressure
@ 10m
Power
Pressure
@ 10m
UCC75D-2/1
Power
81
74
80
77
79
78
72
63
Pressure
@ 10m
49
42
48
45
47
46
40
31
Power
NOT APPLICABLE
Pressure
@ 10m
UCC100D-2/1
Power
81
80
84
78
79
78
72
63
Pressure
@ 10m
49
48
52
46
47
46
40
31
UCC110D-4/2
Power
88
82
89
82
82
84
82
77
Pressure
@ 10m
56
50
57
50
50
52
50
45
UCC125D-3/1
Power
84
74
84
83
81
80
74
65
Pressure
@ 10m
52
42
52
51
49
48
42
33
UCC130D-4/2
Power
88
79
89
84
82
84
82
77
Pressure
@ 10m
56
47
57
52
50
52
50
45
UCC150D-3/1
Power
84
74
84
83
81
80
74
65
Pressure
@ 10m
52
42
52
51
49
48
42
33
UCC160D-4/2
Power
88
79
89
84
82
84
82
77
Pressure
@ 10m
56
47
57
52
50
52
50
45
UCC180D-6/2
Power
90
83
92
86
84
86
84
79
Pressure
@ 10m
58
51
60
54
52
54
52
47
UCC200D-6/2
Power
90
81
91
87
84
86
84
79
Pressure
@ 10m
58
49
59
55
52
54
52
47
UCC225D-6/2
Power
90
81
91
87
84
86
84
79
Pressure
@ 10m
58
49
59
55
52
54
52
47
UCC250D-6/2
Power
90
81
91
87
84
86
84
79
Pressure
@ 10m
58
49
59
55
52
54
52
47
UCC275D-8/2
Power
89
78
85
83
88
85
81
75
Pressure
@ 10m
57
46
53
51
56
53
49
43
UCC300D-8/2
Power
89
78
85
83
88
85
81
75
Pressure
@ 10m
57
46
53
51
56
53
49
43
UCC330D-10/2
Power
90
77
86
84
88
86
80
73
Pressure
@ 10m
58
45
54
52
56
54
48
41
UCC360D-10/2
Power
90
75
86
84
89
86
80
73
Pressure
@ 10m
58
43
54
52
57
54
48
41
UCC400D-12/2
Power
91
78
87
85
89
87
82
75
Pressure
@ 10m
59
46
55
53
57
55
50
43
UCC450D-12/2
Power
91
80
87
85
89
87
83
77
Pressure
@ 10m
59
48
55
53
57
55
51
45
1
dB(A) is the overall sound level, measured on the A scale.
2
All sound data measured at nominal conditions: Water in/out 12/7°C at 30°C ambient.
3
Figures based on standard unit, for units fitted with optional pump packages, please contact Airedale.
The Sound Pressure data quoted is only valid in free field conditions, where the unit is installed on a reflective base. If
the equipment is placed adjacent to a reflective wall, values may vary to those stated, typically increasing by 3dB for
each side added.