CR12-165

CONDENSERS

Condenser

21

Technical Manual :6666879 1.1.0 02_2013

/2012

Mechanical Data- Condensers

CR80

CR95

CR105

Total Heat of Rejection CR

(1)

kW

87.8

110.9

113.2

Dimensions - Horizontal

(2)

H x W x L

mm

1167 x 1000 x 3565

1167 x 1000 x 3565

1167 x 1000 x 3565

Dimensions - Vertical

(2)

H x W x L

mm

1090 x 1167 x 3565

1155 x 1167 x 3565

1090 x 1167 x 3565

Weight

Machine

kg

208

258

260

Construction

Material/Colour

Galvanised Sheet Steel, Epoxy Baked Powder Paint - Light Grey (RAL 7035)

Condenser

Air Cooled - Rifled Copper Tube/Turbulated Aluminium Fins

Dry Cooler

Air Cooled - Copper Tube/Turbulated Aluminium Fins

Total Face Area

3.63

3.63

3.63

Nominal Airflow

m³/s

7.5

10.8

6.6

Discharge

-H Horizontal or -V Vertical (Please Specify at Order)

Fan & Motor

Axial

Quantity

3

3

3

Diameter

mm

630

710

630

Maximum Speed

rpm

895

930

895

Refrigeration - CR

Single Circuit

Refrigerant Type

R410A

Holding Charge

Inert Gas

Coil Volume

l

18.3

18.3

36.6

Refrigerant Charge

(3)

kg

8.4

8.4

16.7

Dry Cooler

Internal Water Volume

L

23.1

23.1

43.2

Water flowrate

l/s

2.0

2.5

2.6

Pressure Drop

kPa

48.5

70

32

Connections

Liquid Line - Sweat

in

7/8

7/8

7/8

Discharge Line - Sweat

in

1 3/8

1 3/8

1 3/8

OPTIONAL EXTRAS

Short Case Axial Fan

Designed to 75 Pa ESP

Dimensions - Horizontal

H x W x L

mm

1167 x 1000 x 3565

1167 x 1000 x 3565

1167 x 1000 x 3565

Dimensions - Vertical

H x W x L

mm

1130 x 1167 x 3565

1140 x 1167 x 3565

1130 x 1167 x 3565

Weight

Machine

kg

242

249

294

EC Fan

Dimensions - Horizontal

H x W x L

mm

1167 x 1000 x 3565

1167 x 1000 x 3565

1167 x 1000 x 3565

Dimensions - Vertical

H x W x L

mm

1127 x 1167 x 3565

1170 x 1167 x 3565

1127 x 1167 x 3565

Weight

Machine

kg

228

293

280

(1) Nominal data based on 35°C ambient and a 50°C mean condensing temperature and using standard fan.