Cus 15 - 60, Condensing units, Noise data – Airedale Condensing Units (CU) 3kW - 80kW User Manual

Page 9

Advertising
background image

Condensing Units

CUS 15 - 60

Chillers & Condensing Units

Technical Manual : v1.2.0 07_2014

9

Noise Data

Sound

Frequency (Hz)

Measurement

dBa

63

125

250

500

1000

2000

4000

8000

Power

dB

84

88

80

81

81

81

74

66

57

CUS 15D

Pressure

@ 1m

76

80

72

73

73

73

66

58

49

Pressure

@ 10m

56

60

52

53

53

53

46

38

29

Power

dB

85

88

80

82

82

82

75

68

59

CUS 20D

Pressure

@ 1m

77

80

72

74

74

74

67

60

51

Pressure

@ 10m

57

60

52

54

54

54

47

40

31

Power

dB

86

88

81

83

83

82

78

72

64

CUS 25/30D

Pressure

@ 1m

78

80

73

75

75

74

70

64

56

Pressure

@ 10m

58

60

53

55

55

54

50

44

36

Power

dB

101

95

93

89

89

95

95

93

91

CUS 40D

Pressure

@ 1m

93

87

85

81

81

87

87

85

83

Pressure

@ 10m

73

67

65

61

61

67

67

65

63

Power

dB

103

97

95

92

92

98

98

95

90

CUS 50D

Pressure

@ 1m

95

89

87

84

84

90

90

87

82

Pressure

@ 10m

75

69

67

64

64

70

70

67

62

Power

dB

105

98

95

92

94

99

100

97

90

CUS 60D

Pressure

@ 1m

97

90

87

84

86

91

92

89

82

Pressure

@ 10m

77

70

67

64

66

71

72

69

62

Notes:

1

Sound Power Reference Power = 10-12 Watts.

2

Sound Pressure Reference Pressure = 2 x 10-5 N/m2.

3

dBA is the overall noise level, measured on the A scale.

4

Sound Pressure data is only valid in free field conditions, where a reflective base, such as a roof is found.