OWNER'S SERVICE MANUAL

NO. 05601

INSPECTION, MAINTENANCE AND

RECHARGE

































REFERENCES IN THIS MANUAL

AVAILABLE FROM

NFPA-10 Portable Fire Extinguishers

National Fire Protection Association

P. O. Box 9101
Quincy, MA 02269-9101


CGA C-1
Methods for Hydrostatic Testing

Compressed Gas Association

of Compressed Gas Cylinders

1235 Jefferson Davis Hwy, Suite 501

CGA C-6 Standard for Visual Inspection

Arlington, VA 22202

of Compressed Gas Cylinders

All fire extinguishers should be installed, inspected and maintained in
accordance with the National Fire Protection Association standard titled
"Portable Fire Extinguishers", NFPA-10 and the requirements of local
authorities having jurisdiction.

When maintenance is indicated it should be performed by trained persons
having proper equipment. Fire extinguishers are pressure vessels and must
be treated with respect and handled with care. They are mechanical
devices and require periodic maintenance to be sure that they are ready to
operate properly and safely. Amerex strongly recommends that the
maintenance of portable fire extinguishers be done by a trained professional
– your local authorized Amerex Distributor.

Amerex Corporation makes original factory parts available to insure proper
maintenance

– use of substitute parts releases Amerex of its warranty

obligations. Amerex parts have machined surfaces and threads that are
manufactured to exacting tolerances. O-rings, hoses, nozzles, horns and all
metal parts meet precise specifications and are subjected to multiple in-
house inspections and tests for acceptability. There are substitute parts
available that are incorrectly labeled as UL component parts, some are
advertised as Amerex type. None of these meet UL requirements and all of
them void the Amerex extinguisher warranty and UL listing. DO NOT
SUBSTITUTE.

WARNING

Do not use this extinguisher on Class C fires involving energized
electrical equipment, Class D fires or any flammables that will react
with water. Protect from freezing unless charged with an Amerex
Model 506 Loaded Stream/Anti-freeze Charge.

AMEREX CORPORATION

– P.O. BOX 81 – TRUSSVILLE, ALABAMA 35173-0081

Phone: 205/655-3271 Fax: 800/654-5980

e-mail:

[email protected]

Web Page:

http://www.amerex-fire.com

Printed in U.S.A.

0M05601F Rev. 3/11

STORED PRESSUR

E

STAINLESS STEEL

WATER

FIRE EXTINGUIS

HERS

Model 2

40

-

2

-1/2

G

allon

Advertising