INSTALLATION

Your layout and particular hazards dictate the placement of fire extinguishers. NFPA-10
requires that hand portable extinguishers with a gross weight less than 40 lbs. be hung with
the top of the extinguisher not more than 5 ft. (1.53 m) above the floor. Extinguishers
having a gross weight greater than 40 lbs. (18.14 kg) should be installed so that the top of
the extinguisher is not more than 3 ½ ft. (1.07m) above the floor. All extinguishers should
be in an accessible location and near an exit. Never install the extinguisher in a
location where a potential hazard would prevent easy access
. The operational
temperature range for this extin guis her is -65°F to +120°F (-54°C to +49°C) or -40°F to
+120°F (-40°C to +49°C) [please see the nameplate on your extinguisher]. The
extinguisher should be adequately protected if temperatures outside of this range are
anticipated. Keep the extinguisher clean and free from dirt, ice, chemicals and any
contaminants that may interfere with its proper operation. DO NOT FUNCTIONALLY TEST
THIS FIRE EXTINGUISHER. (Testing or any use may cause the extinguisher to gradually
lose pressure over a period of time and make the extinguisher ineffective.) Never throw an
extinguisher into a fire because rapid heat buildup could cause pressure expansion and
exceed the limitations of the cylinder.








OPERATION




NOTE:

Persons expected to use this extinguisher should be trained in initiating its
operation and in the proper firefighting technique. Familiarize all personnel
with this information before an emergency occurs.


1. Remove the extinguisher from wall hanger or bracket.
2. Hold the extinguisher upright, twist and pull the ring (safety) pin, snapping the plastic

lockwire seal.

3. Starting back a minimum of 8 feet from the fire, grasp the nozzle and aim at the base of

the fire nearest you.

4. Keeping the extinguisher upright, squeeze the lever to discharge and sweep the

chemical agent stream from side to side. Work the fire away from you while being alert
for flashbacks. Move closer as the fire is extinguished but not so close as to scatter or
splash the burning material.

5. When the fire is out, stand by and watch for possible re-ignition.
6. Evacuate and ventilate the area immediately after extinguishing the fire. The fumes and

smoke from any fire may be hazardous and can be deadly.

CAUTION:

DISCHARGE TIME AND EFFECTIVE RANGE OF THE AGENT THROW
VARIES ACCORDING TO MODEL

– SEE THE SPECIFICATION

LITERATURE FOR YOUR EXTINGUISHER.

RECHARGE FIRE EXTINGUISHERS IMMEDIATELY AFTER ANY USE

Advertising