12.

Reconnect the hose to the operating valve. Properly coil the hose on the rack and install the nozzle (with
the lever in a closed position) on the mount. (See Page 12 - Tech Tip)

CAUTION: WHEN ASSEMBLING THE HOSE TO THE AGENT CYLINDER OR NOZZLE TO THE HOSE,

TIGHTEN THE COUPLING ¼ TURN AFTER CONTACTING THE HOSE GASKET.

13.

Install the Ring (Safety) pin and lockwire (tamper) seal. Record recharge date and attach new recharge tag.

14.

Weigh assembled extinguisher and confirm that the total weight is within the allowable tolerances indicated
in the “Maintenance” section of the nameplate (label).

15.

Return the extinguisher to its proper location.