TECHNICAL DATA

TECHNICAL DATA FOR ANALOG VALVE

POSITIONER SRI990 -B / -C

Input

Two-wire system

Reverse polarity protection. . standard feature

Interlock diode . . . . . . . . . . . standard feature

Signal range . . . . . . . . . . . . 4 to 20 mA

Characteristic. . . . . . . . . . . . linear to rotation angle

1)

Operating range. . . . . . . . . . 3 to 21.5 mA

Input voltage . . . . . . . . . . . . DC 12 to 36 V

2)

(unloaded)

Load . . . . . . . . . . . . . . . . . . 300 Ω, 6 V at 20 mA

Configuration

with switches:

Rotation. . . . . . . . . . . . . . . . clockwise or counter clockw.

Input signal . . . . . . . . . . . . . 4 to 20 mA (direct)

20 to 4 mA (inverse)

Split range

1) 3)

. . . . . . . . . . . 4 to 12 mA, 12 to 20 mA

(by means of Dip switch)

20 to 12 mA, 12 to 4 mA

with potentiometers: . . . . . Zero (ZERO)

Span (S)

Gain (G)

Damping (D)

Travel indication

mechanical (display window), for rotary or stroke actuator

transmission . . . . . . . . . . . . 1:2 or 1:6 switchable

Output

Action . . . . . . . . . . . . . . . . . single or double acting

Output to actuator . . . . . . . . 0 to ~ 100 % of supply air
Pneumatic connection

NAMUR mounting . . . . . . . . G 1/4 for pipe diameter 6 to

12 mm (0.24 to 0.47 in) for air

supply and outputs y1, y2 to

the actuator;

1/4 - 18NPT with additional

connection manifold

Direct mounting . . . . . . . . . . Instead of the output y1 an

airconnection on the rear side

with O-ring will be

used(closed at NAMUR

mounting).

Electrical connection

Line entry. . . . . . . . . . . . . . . 1 or 2 cable glands 1/2-14 NPT

or M20 x1.5

(others with Adapter AD-...)

Cable diameter . . . . . . . . . . 6 -12 mm (0.24 - 0.47 in)

Screw terminals . . . . . . . . . . terminals 11 +, 12 – for input,

I– for current measurement

optional . . . . . . . . . . . . . . 4 additional terminals for

limit switch signals

Wire cross section . . . . . . . . 0.3 - 2.5 mm² (AWG 22 - 14)

Test sockets Ø 2 mm . . . . . . integrated in terminals, for

non- interruptable current

measurement

Weight

Single acting . . . . . . . . . . . . approx. 1.7 kg (3.7 lbs)

Double acting. . . . . . . . . . . . approx. 2.0 kg (4.4 lbs)

Materials

Housing . . . . . . . . . . . . . . . . aluminum (Alloy No. 230)

finished with DD varnish

All moving parts of

feedback system . . . . . . . . . 1.4306 / 1.4571 / 1.4104

Mounting bracket . . . . . . . . . aluminum (Alloy No. 230)

Mounting

Attachment to stroke actuators

- direct . . . . . . . . . . . . . . . . . with attachment kit EBZG -D

- direct, FoxPak, FoxTop . . . with attachment kit EBZG -E

- for casting yoke acc. to

IEC 534-6 (NAMUR) . . . . . with attachment kit EBZG -H

- for pillar yoke acc. to

IEC 534-6 (NAMUR) . . . . . with attachment kit EBZG -K

Attachment to rotary actuators

- acc. to VDI/VDE 3845 . . . . with attachment kit EBZG -R
– Further attachment kits see “Model Codes Attachment Kits”
Mounting orientation. . . . . . . see “DIMENSIONS”

Ambient conditions

Operating conditions

acc. to IEC 654-1 . . . . . . . . . the device can be operated

at a classe Dx location

Ambient temperature . . . . . . –40 to 80 °C (–40 to 176 °F)

Relative humidity . . . . . . . . . up to 100 %

Transport and storage

Ambient temperature . . . . –40 to 80 °C (–40 to 176 °F)

Storage conditions according to IEC 60721-3-1:

1K5; 1B1; 1C2; 1S3; 1M2

Protection class

according to IEC 529 . . . . IP 65

4)

, IP 66

4)

on request

according to NEMA. . . . . . Type 4X

4)

Electromagnetic compatibility EMC

Operating conditions . . . . . . industrial environment

Immunity according to

- NAMUR recommendation NE21 fulfilled

- EN 61 326 . . . . . . . . . . . . . fulfilled

- EN 61 000-6-2 . . . . . . . . . . fulfilled

Emission according to

- EN 55 011,

Group 1, Class A . . . . . . . . fulfilled

- EN 61 000-6-2 . . . . . . . . . . fulfilled

Offline diagnosis

Test possibility for pneumatic control

1) The digital positioner SRI990 offers enlarged functionality

2) On request we can specify higher voltage limits

3) At maximum rotation angle range of 30 degrees

(± 15 degrees around center position of feedback lever).

Split range is not available for actuators with a swivel range >30 degrees