Menu 4: Characteristic of Setpoint

SRD Main Menu

2 Autostart

3 Valve Action

4 Valve Char.

4 Valve Char.

4.1 Linear

4.2 Eq Perc 1:50

4.3 Quick open

4 Valve Char.

4.1 Linear

4.2 Eq Perc 1:50

4.3 Quick open

M

1

2

3

4

½

-

-

-

½

M and LED 4 flash

A relationship between the input signal and valve position is set.

-

1

-

-

-

LED 1 lights up

4.1 “Linear”. See Fig. 4.1

-

-

1

-

-

LED 2 lights up

4.2 “Equal percentage”: Results in an equal percentage characteristic line
with a position ratio of 1:50 for a valve of linear characteristic.
See Fig. 4.2

-

-

-

1

-

LED 3 lights up

4.3 “Inverse equal perc.”: Results in an inversely equal percentage charac-
teristic line with a position ratio of 50:1 for a valve of linear characteristic.
See Fig. 4.3

3

.

4

.

g

i

F

2

.

4

.

g

i

F

1

.

4

.

g

i

F

-

-

-

-

1

LED 4 lights up

“User defined characteristic”:
A characteristic line entered via
communication (not via local keys) with
2 to 22 supporting points) is activated.
A linear characteristic is factory set.

4 Valve Char.

4.2 Eq Perc 1:50

4.3 Quick open

4.4 Customer