Step 1

Where would you like your displayed flow rate decimal point located?

Desired Location

=

D (Decimal Rate Factor) Note: Four decimal places maximum.

r

XXXXX

= 1

XXXX.X

= 10

XXX.XX

= 100

XX.XXX

= 1000

X.XXXX

= 10000

Enter your D here.

r

Step 2

What time factor would you like to use in your measurement?

Example:

Per Minute = 60 seconds

Per Hour

= 3600 seconds

Per Day

= 86400 seconds

Fill in the amount of seconds you desire here.

Step 3

To determine your flow rate K-Factor, the following information is needed.

a. What size pipe you are going to install this meter on?

inch pipe

b. What schedule pipe are you using?

Sch 40 or

Sch 80 or

Inline

c. What is your flow range?

Low Flow or

Standard Flow (refer to pages 16 & 17)

d. Using the data you specified above, locate your K-Factor from the correct table. Pages 16 & 17.

e. What is your K-Factor?

f. If you are going to be using gallons as your unit of measure, you can go directly to Step 4.

g. To convert K-Factor to other units of measure, use the following formulas:

Ounces

= K-factor ÷ 128

Liters

= K-factor ÷ 3.785

Cubic Meters

= K-factor ÷ 0.003785

Example: To convert 2” schedule 80 gallons K-factor to

liters, you will use the following formula:

Note: Locate your K-factor off the table on pages 16 & 17..

58.82 (K-factor)

3.785

= 15.54

Your new liters K-factor is 15.54

Write your new K-Factor number here.

F-2000

Page 12

! Press

to toggle between RATE and TOTAL display modes. The icon will

light to indicate the active mode.

! Press and hold

for at least 1.25 seconds to enter the programming mode.

Allow twenty seconds to pass so the display will switch back to the readout

mode. See section 7.1.

! While the TOTAL mode is displayed, press

to reset the total amount to

zero. (Must be enabled in the program mode - see page 24, step 6.)

ENTER

ENTER

TOTAL

CLEAR

0

RATE TOTAL

00000

RATE

0

TOTAL

7.2.3 How Do I Determine My Calibration Numbers?

When ordered as a complete system, the F-2000 MODEL RT is factory programmed to the flow range you specified when
you placed your order. See section 4.0 for various flow ranges.

Note: The F-2000 model AO and PC functions will always require field programming. All F-2000 models will require field
programming when components are purchased separately. See section 7.2 and 7.3.

The following screens are used to input the calibration constants and to turn on or off the various features of the MODEL
RT. The MODEL RT has six different input screens. They are listed in the table below.

Screen No.

Programming Functions

RATE

1

RATE

2

RATE

3

TOTAL

1

TOTAL

2

TOTAL

3

Toggle Battery Saving mode - on / off (factory default: off)

Toggle front panel Clear Total button - on (enabled) / off (disabled) -- (factory default: off)

Before programming the unit, the following calibration constants must be determined. Remember, when
purchased as a complete system, the model RT is pre-programmed at the factory. No further programming is
necessary.

7.2.2 What Features Are Available On The MODEL RT?