Caleffi 6000 User Manual

Page 29

Advertising
background image

4

Technical specifications

Valve body
Materials:

Body:

brass EN 12165 CW617N

Ball: - versions 3/4”-1 1/4”:

brass EN 12165 CW614N, chrome plated

- versions 1 1/2”-2”:

brass EN 12165 CW614N, chrome plated, POM

- flanged versions:

stainless steel AISI 316

Hydraulic seals:

threaded versions: EPDM - flanged versions: NBR

Maximum working pressure (static):

10 bar

Maximum inlet temperature:

100°C

Temperature gauge scale:

0–80°C

Hot and cold water connections:

3/4”–2”M with union

Mixed water connection:

3/4”–2” F with union

Flanged connections:

DN 65 and DN 80, PN 16

can be coupled with counterflange EN 1092-1

Actuator for threaded version
Electric supply:

230 V (ac)- 50/60 Hz directly from the regulator

Power consumption:

6 VA

Protection cover:

self-extinguishing V0

Protection class:

IP 65

Ambient temperature range:

-10–55°C

Electric supply cable length:

0,8 m

Actuator for flanged version
Electric supply:

230 V (ac)- 50/60 Hz directly from the regulator

Power consumption:

10,5 VA

Protection cover:

self-extinguishing V0

Protection class:

IP 65

Ambient temperature range:

-10–55°C

Electric supply cable length:

2 m

Digital regulator
Materials:

Housing:

self-extinguishing ABS,

white RAL 1467

Cover:

self-extinguishing SAN, smoked transparent

Electric supply:

230 V (ac) 50/60 Hz

Power consumption:

6,5 VA

Adjustment temperature range:

20–85°C

Disinfection temperature range:

40–85°C

Ambient temperature range:

0–50°C

Protection class:

IP 54 (wall mounting)

(Class II appliance)

Contact rating:

Mixing valve control:

5(2) A / 250 V

Alarm relay (R2):

5(2) A / 250 V

Relay 1, 3, 4:

10(2) A / 250 V

Fuses: 1 (main):

80 mA

Fuses: 2 (mixing valve):

1 A

Charge reserve:

15 days in the event of a electric supply

failure, with a 3-cell rechargeable 150 mAh buffer battery

Enabled by microswitch.

Battery charging time:

72 h

Conforms to Directives:

CE

Temperature probes
Materials:

Body:

stainless steel

Type of sensitive element:

NTC

Working temperature range:

-10–125°C

Resistance:

10000 Ohm at 25°C

Time constant:

2,5

Max. distance for flow or return probe:

150 m with cable 2x1 mm

2

250 m cable 2x1,5 mm

2

Mixing valve performance
Accuracy:

±2°C

Maximum working pressure (dynamic):

5 bar

Maximum ratio of inlet pressures

(H/C or C/H) with G

min

= 0,5 Kv:

2:1

*

∆p = 1,5 bar

Recommended flow rates to ensure stable operation and an
accuracy of ± 2°C

Size

Kv (m

3

/h)

3/4”

8,4

1”

10,6

1 1/4”

21,2

1 1/2”

32,5

2”

41,0

DN 65

90,0

DN 80

120,0

Size

Min (m

3

/h)

Max (m

3

/h)*

3/4”

0,5

10,3

1”

0,7

13,2

1 1/4”

1,0

28,1

1 1/2”

1,5

39,0

2”

2,0

48,3

DN 65

4,0

110,0

DN 80

5,0

146,0

Advertising