Dwyer instruments, inc – Dwyer 1950 User Manual

Page 2

Advertising
background image

INSTALLATION
1. Select a location free from excess vibration and corrosive atmos-
pheres where temperatures will be within the limits noted under
Specifications on reverse. Switch may be installed outdoors or in areas
where the hazard of explosion exists. See reverse for specific types of
hazardous service.

2. Mount standard switches with the diaphragm in a vertical plane and
with switch lettering and nameplate in an upright position. Some switch-
es are position sensitive and may not reset properly unless they are
mounted with the diaphragm vertical.

3. Connect switch to source of pressure, vacuum or differential pressure.
Metal tubing with 1/4″ O.D. is recommended, but any tubing which will
not restrict the air flow can be used. Connect to the two 1/8″ female NPT
pressure ports as noted below:

A. Differential pressures - connect pipes or tubes from source
of greater pressure to high pressure port marked HIGH
PRESS, and from source of lower pressure to low pressure
port marked LOW PRESS.

B. Pressure only (above atmospheric pressure) - connect
tube from source of pressure to high pressure port. The low
pressure port is left open to atmosphere.

C. Vacuum only (below atmospheric pressure) - connect tube
from source of vacuum to low pressure port. The high
pressure port is left open to atmosphere.

4. To make electrical connections, remove the three hex head screws
from the cover and after loosening the fourth captive screw, swing the
cover aside. Electrical connections to the standard single pole, double
throw snap switch are provided by means of terminals marked “COM”
(common), “NO” (norm open), “NC” (norm closed). The normally open
contacts close and the normally closed contacts open when pressure
increases beyond the set point. Switch loads for standard models should
not exceed the maximum specified current rating of 15 amps resistive.
Switch capabilities decrease with an increase in ambient temperature,
load inductance, or cycling rate. Whenever an application involves one
or more of these factors, the user may find it desirable to limit the
switched current to 10 amps or less in the interest of prolonging switch
life.

ADJUSTMENT: To Change the Set point
1. Remove the plastic cap and turn the slotted Adjust-ment Screw at the
top of the housing clockwise to raise the set point pressure and counter-
clockwise to lower the set point. After calibration, replace the plastic cap
and re-check the set point.

2. The recommended procedure for calibrating or checking calibration is
to use a “T” assembly with three rubber tubing leads, all as short as pos-
sible and the entire assembly offering minimum flow restriction. Run one
lead to the pressure switch, another to a manometer of known accuracy
and appropriate range, and apply pressure through the third tube. Make
final approach to the set point very slowly. Note that manometer and
pressure switch will have different response times due to different inter-
nal volumes, lengths of tubing, fluid drainage, etc. Be certain the switch
is checked in the position it will assume in use, i.e. with diaphragm in a
vertical plane and switch lettering and Dwyer nameplate in an upright
position.

3. For highly critical applications check the set point adjustment and if
necessary, reset it as noted in step A.

MAINTENANCE
The moving parts of these switches need no maintenance or lubrication.
The only adjustment is that of the set point. Care should be taken to keep
the switch reasonably clean. Periodically the vent drain plug should be
rotated, then returned to its original position. This will dislodge deposits
which could accumulate in applications where there is excessive con-
densation within the switch. The Series 1950 Explosion-Proof Differential
Pressure Switch is not field serviceable and should be returned if repair
is needed (field repair should not be attempted and may void warranty).
Be sure to include a brief description of the problem plus any relevant
application notes. Contact customer service to receive a return goods
authorization number before shipping.

3-1/2

[88.9]

3/8

[9.53]

1-7/16

[36.5]

1/8 NPT(F)

PRESSURE

PORT

1-11/16

[42.9]

1/8 NPT(F)

HIGH PRESSURE

PORT

1/2 NPT(F)

ELEC.

CONDUIT

CONNECTION

RANGE ADJUSTMENT

SCREW

17/64 [6.75] DIA MTG

HOLES (2)

4-7/8

[123.8]

5-7/16

[138.1]

VENT DRAIN

PLUG

1950 Switch Outline Dimensions

©Copyright 2012 Dwyer Instruments, Inc.

Printed in U.S.A. 1/12

FR# 26-440332-00 Rev. 13

DWYER INSTRUMENTS, INC.

Phone: 219/879-8000

www.dwyer-inst.com

P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A.

Fax: 219/872-9057

e-mail: [email protected]

1950-02: 7-3/4˝ (196.9) dia. x 4-11/32˝
(110.3) depth. For complete dimensions
request drawing 28-700175-00 from our
Customer Service Department

Advertising