Dwyer instruments, inc – Dwyer 616D User Manual

Page 2

Advertising
background image

ELECTRICAL CONNECTIONS
CAUTION: Do not exceed specified supply voltage ratings.
Permanent damage not covered by warranty will result. This unit is
not designed for 120 or 240 volts AC line operation.

Electrical connections are made to the terminal block located in front of
the transmitter. Terminals are marked + and - (See Figure B below).

Figure B

Wire Length
The maximum length of wire connecting transmitter and receiver is a
function of wire size and receiver resistance. Wiring should not
contribute more than 10% of the receiver resistance to total loop
resistance. For extremely long runs (over 1000 feet), choose receivers
with higher resistance to minimize size and cost of connecting leads.
Where wiring length is under 100 feet, hook-up wire as small as 22 AWG
can be used.

2-Wire Operation
An external power supply delivering 10-35 VDC with minimum current
capability of 40 mA DC (per transmitter) must be used to power the
control loop. See Figure C for connection of the power supply,
transmitter and receiver.
The range of appropriate receiver load
resistance (R

L

) for the DC power supply voltage available is expressed

by the formula and graph in Figure D. Shielded two wire cable is
recommended for control loop wiring. If grounding is required, use the
negative side of the control loop after the receiver. Otherwise, in 2-wire
operation it is not necessary to observe polarity of control loop
connections.

2-Wire Connections

Figure C

Power Supply Voltage – VDC (2-wire)

Figure D

Calibration Check
Each Series 616D Transmitter is factory calibrated to the range given in
the model chart. To check calibration and adjust if necessary, the
following procedure should be used. For purposes of clarification in these
instructions, range is defined as that pressure which, applied to the
transmitter, produces 20 milliamps of current in the loop. Zero pressure
is always assumed to be 4 milliamps.

1. With the transmitter connected to the companion receiver, insert an

accurate milliameter in series with the current loop. The milliameter
full scale range should be 30 mA or greater.

2. Connect a controllable pressure source to one leg of a tee with the

other two legs connected to the high pressure port of the transmitter
and the third leg to an accurate test gage or manometer, in an
appropriate range. The low pressure port should be vented to
atmosphere. Calibration must be performed with the unit in the same
position in which it will be mounted.

3. Apply electrical power to the unit and allow it to stabilize for 10

minutes.

4. With no pressure applied to the transmitter, adjust ZERO control so

that loop current is 4 mA. See Figure B.

5. Apply full range pressure and adjust loop current to 20 mA using

SPAN control. See Figure B.

6. Relieve pressure and allow transmitter to stabilize for 2 minutes.
7. Zero and span controls are slightly interactive, so repeat steps 4

through 6 until zero and full range pressures consistently produce
currents of 4 and 20 mA respectively.

8. Remove the milliameter from the current loop and proceed with final

installation of the transmitter and receiver.

Voltage Input
Series 616D Transmitters can be easily adapted for receivers requiring
1-5 or 2-10 VDC inputs. Insert a 249 ohm, (1-5 VDC) or 499 ohm (2-10
VDC) resistor of the proper power rating in series with the current loop
but in parallel with the receiver input. Locate this resistor as close as
possible to the input. Because resistor accuracy directly influences
output signal accuracy, we recommend use of a precision ±0.1%
tolerance resistor to minimize this effect.

MULTIPLE RECEIVER INSTALLATION
An advantage of the standard 4-20 mA DC output signal produced by the
Series 616D Transmitter is that any number of receivers can be
connected in series in the current loop. Thus, an A-701 Digital Readout,
an analog panel meter, a chart recorder, process controlling equipment
or any combination of these devices can be operated simultaneously.
The only requirement is that each component be equipped for a standard
4-20 mA input and the proper polarity of the input connections be
observed when inserting the device in the current loop. If any of the units
display a negative or downscale reading, the signal input leads are
reversed.

MAINTENANCE
Upon final installation of the Series 616D Differential Pressure
Transmitter and the companion receiver, including the A-701 Digital
Readout, no routine maintenance is required. A periodic check of the
system calibration is recommended following the procedures explained
under Calibration Check. The Series 616D Transmitter is not field
serviceable and should be returned, freight prepaid, to the factory if
repair is required. Please enclose a description of the problems
encountered plus any available application information. The A-701
should be returned directly to its manufacturer for service. See the A-701
instructions for address.

POWER

SUPPLY

10-35 VDC

PRESSURE

TRANSMITTER

RECEIVER

1500
1400
1300
1200
1100
1000

900
800
700
600
500
400
300
200
100

50

Total Receiver Resistance ()

Maximum Value (1250 )

R Max. =

0 5 10 13 15 20 25 30 35 40

L

Vps–10.0
20mA DC

Operating

Region

©Copyright 2010 Dwyer Instruments, Inc.

Printed in U.S.A. 6/10

FR# 01-443269-00 Rev. 2

DWYER INSTRUMENTS, INC.

Phone: 219/879-8000

www.dwyer-inst.com

P.O. BOX 373 • MICHIGAN CITY, INDIANA 46361, U.S.A.

Fax: 219/872-9057

e-mail: [email protected]

SPAN AND ZERO

ADJUST

ELECTRICAL

CONNECTIONS

A

E-43-D:E-43-D 6/2/10 9:51 AM Page 2

Advertising