Simultaneous Current and Voltage Operation

The connection to the transmitter are made to Terminals 1, 2, and 3 on the terminal
block as shown in Figure 4. The terminal block is removable and each of the
terminals are labeled underneath the terminal block on the circuit board. Polarity
is indicated by PWR, COM, and +VOUT. The AC/DC selection jumper should be set
for DC operation. The voltage output and the power supply must have separate
wire leads that are only joined at terminal 2 of the transmitter. Additional error may
occur for the voltage output if a single wire is used or if the wires are joined at the
power supply or receiver.

figure 4

For the current output, the maximum allowable loop resistance (wiring + receiver
resistance) is dependent on the power supply. The maximum loop voltage drop
must not reduce the transmitter voltage below 17 V. The maximum loop resistance
can be calculated using the following equation:

R

MAX

= (VPS – 17.0) / 0.02 Where VPS is the power supply voltage

The equation uses 17.0 instead of 10.0 used in current only equation. This
represents the minimum voltage supply which is higher on the simultaneous output
configuration due to the requirements of the voltage outputs.

Shielded 4-wire cable is recommended for control loop wiring. Ground the shield at
the power supply end only. Should the polarity of the transmitter or receiver be
inadvertently reversed, the unit will not function properly, but no damage will be
done to the transmitter.

For voltage outputs, the minimum receiver load is 1K Ω. The resistance due to the
wire should be low compared to the receiver load resistance. While the voltage at
the terminal block remains unchanged with a 10 mA current flow, resistive losses in
the wiring do cause errors in the voltage delivered to the receiver. For a 1%
accurate gauge, the resistance of the wires should be less than 0.1% of the value
of the receiver load resistance. This will keep the error caused by the current flow
below 0.1%.

The output across +VOUT and COM will be either 0 to 5 V, 0 to 10 V, or the inverse
depending on the dip switch setting. See Dip Switch Setting Section for more
information.

DIP SWITCH SETTINGS
DIP Switches can be located next to the terminal block as shown in Figure 5. A
small screw driver or pen can be used to change the position of the switches.

figure 5

factory Settings
Mode = Unidirectional
Range = Highest Range Setting (0.5, 5, or 28 in w.c.)
Units = Inches W.C.
Voltage Output Range = 10 V
Direct / Reverse Output Action = Direct

Setting the Pressure Range
Ranges are selected by adjusting DIP Switch Positions 1 and 2 according to the
below tables. The range also depends on the units selected (Refer to Setting the
Engineering Units Section) and if the input is set for unidirectional or bidirectional
(Refer to the Setting for Unidirectional or Bidirectional Section). The tables below
show the maximum full scale value for the selected range and selected units. If the
unit is set to unidirectional, the ranges are all zero based. If the unit is set for
bidirectional, the ranges will be ± the maximum full scale value shown in the tables
below.

Setting for Unidirectional or Bidirectional
The Models MS2-X101 and MS2-X103 can be set to measure pressure in one
direction or two directions based on the setting of DIP Switch 3. The Model MS2-
X102 can only be set to unidirectional.

• When the switch is in the ON direction, the transmitter will be set for Unidirectional
and will be 0 based (i.e. 0 to 5 in w.c.).
• When the switch is in the OFF position, the transmitter will be set for Bidirectional
and will be ± the maximum of the selected range (i.e. ±5 in w.c.).
• For unidirectional units only, switch has no effect and unit will remain in
unidirectional mode.

DIP Switch

full Scale Range for MS2-X101

1

OFF
OFF

ON
ON

2

OFF

ON

OFF

ON

in w.c.

0.1

0.15
0.25

0.5

Pa

25
40
50

125

mm w.c.

2.5

4
6

10

kPa

0.025
0.040
0.050
0.125

DIP Switch

full Scale Range for MS2-X102

1

OFF
OFF

ON
ON

2

OFF

ON

OFF

ON

in w.c.

1
2
3
5

Pa

250
500
750

1250

mm w.c.

25
50
75

125

kPa

0.250
0.500
0.750

1.25

DIP Switch

full Scale Range for MS2-X103

1

OFF
OFF

ON
ON

2

OFF

ON

OFF

ON

in w.c.

10
15
25
28

Pa

2500
3500
5000
6975

mm w.c.

250
350
500
700

kPa

2.50
3.50
5.00
6.98

11 22 33

11

22

33

44

55

66

77

ZERO

ZERO

SPAN

SPAN

POWER

VOLTAGE

RECEIVER

CURRENT

RECEIVER

++

++

++

__

__

__

NOTE - POWER

AND VOLTAGE

RECEIVER "-" MUST

BE SEPERATE WIRES

AND BOTH WIRED TO

SIMULTANEOUS CURRENT AND

VOLTAGE OUTPUT WIRING

11 22 33

11

11

22

22

33

33

44

44

55

55

66

66

77

77

ZERO

ZERO

SPAN

SPAN

ON

ON

DIP SWITCH SETTINGS

DIP SWITCH SETTINGS

RANGE

RANGE

UNITS

UNITS

10V

10V

DIR

DIR

5V

5V

REV

REV

UNIDIRECTIONAL

UNIDIRECTIONAL

BIDIRECTIONAL

BIDIRECTIONAL

All power should be turned off to the transmitter before adjusting
the dip switch settings to avoid electrical shock.

WaRNING

DO NOT EXCEED SPECIFIED SUPPLY VOLTAGE RATINGS.
PERMANENT DAMAGE NOT COVERED BY WARRANTY

WILL RESULT. SIMULTANEOUS OUTPUTS ARE NOT DESIGNED FOR AC
VOLTAGE OPERATION.

CaUTION