Dwyer DPML-5 User Manual

Dwyer instruments, inc, Series dpml-5 lcd digital panel meter, Bulletin g-61-5

Advertising
background image

Series DPML-5 LCD Digital Panel Meter

Specifications - Installation and Operating Instructions

Bulletin G-61-5

DWYER INSTRUMENTS, INC.

Phone: 219/879-8000

www.dwyer-inst.com

P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A. Fax: 219/872-9057

e-mail: [email protected]

SPECIFICATIONS
Input:
0 to 200 mVDC, 0 to 5 VDC, or 0 to 10 VDC.
Input Impedance: 390KΩ nominal.
Accuracy: ±(0.1% FS + 2 count).
Power Supply: 12 VDC or 24 VDC.
Backlight Power Supply: 24 VDC @ 35 mA typical.
Span and Zero: Adjustable (+19999 counts).
Display: 4-1/2 digits, 7 segments, 0.45˝ (11.4 mm) H.
Decimal Points: 4-position, user selectable.
Engineering Units: DPML-XXX: °F, °C, %, PSI; DPML-XXXP: V, A,
KW, PF.
Polarity: Automatic, “-” displayed.
Operating Temperature: 32 to 122°F (0 to 50°C).
Storage Temperature: -4 to 158°F (-20 to 70°C).
Mounting: Snap-in bezel mount.
Connection: Screw terminals.
Conversion Rate: 3 per second.
Warm-Up: 10 minutes typical.
Weight: 2 oz (56.7 g).
Agency Approvals: RoHS.

P Models

°F

°C

PSI

%

V

A

KW

PF

1-5/8

[41.1]

63/64

[25.1]

1/8

[3]

1-9/64

[29]

2-35/64

[64.5]

2-13/32

[61]

1

[25.4]

2.390 REAR HOUSING

[60.6]

PANEL CUTOUT FOR

WINDOW MOUNTING

The Series DPML-5 LCD Digital Panel Meter is easy-to-read, even at
a distance. The meter is designed with a large 4-1/2 digit LCD display
with a choice of red, amber or green segments. The meter features
adjustable zero and span, user selectable decimal point position, and
selectable 12 VDC or 24 VDC power supply. The backlight requires a 24
VDC power supply. Installation is quick with the snap-in bezel mounting.

INSTALLATION
The Series DPML-5 is designed to snap into a 2.4” W x 1” H (61 x 25.4
mm) panel cutout. No additional hardware is required.

WIRING

The unit is powered by a 12 or 24 VDC power supply and the screw
terminals for wiring are located on the back of the adder board marked
with + PWR - (see Figure 2). Move the power select jumper for the
appropriate power supply value. The backlighting requires a 24 VDC
power supply and should be connected to terminals identified with
+ B/L -.

Figure 1

Figure 2

The unit accepts 5 VDC, 10 VDC or 200 mV connected to terminals
identified with + SIG –. Wire input according to Figure 1. Set the signal
select jumper for the appropriate input (see Figure 3).

Figure 3

Advertising