Dwyer OLS User Manual

W.e. anderson div., dwyer instruments, inc

Advertising
background image

Compact and rugged this optical level switch provides rapid
response while employing no moving parts for stable process con-
trol. The bright red and green LED’s indicate the presence or
absence of liquid for true, local indication. Three material options,
316SS, Polysulfone and PFA, provide application flexibility.
Compact switch can be easily mounted horizontally or vertically.

APPLICATIONS

The model OLS Optical Level Switch maintains predetermined lev-
els in liquid holding tanks, sumps, air conditioning systems,

hydraulic reservoirs, pharmaceutical and beverage systems.

PRINCIPLE OF OPERATION

The optical level switch employs an infrared LED which transmits
infrared light. This light is sent through a prism and reflected back
to a photo-transistor utilizing two 90° light reflections. With the
prism surrounded by a gas, the light source is cast back to the
photo-transistor. When a translucent liquid is introduced to the
prism at or above the point where the light source makes contract
with the prism, the light is reflected into the liquid, not allowing the
photo-transistor to energize.

SPECIFICATIONS

Service: Noncoating compatible liquids.
Wetted Materials: See model chart.
Temperature Limit: Process: OLS-10, 11: 200°F (93.3°C),
OLS-12: 120°F (48.9°C); Ambient: OLS-10, 11: 175°F (79.4°C),
OLS-12: 120°F (48.9°C).
Pressure Limit: OLS-11, 12: 200 psig (13.8 bar), OLS-10:
1000 psig (69 bar).
Repeatability: ±0.02˝ (0.5 mm).
Switch Type: NPN open collector.
Power Requirements: 10 to 28 VDC.
Output Signal: Vout (max) = 28 VDC, Isink (max) = 100 mA.
Current Consumption: 35 mA maximum.
Electrical Connections: 38˝ (965.2 mm) 3 conductor cable,
22 AWG wire.
Process Connection: 1/2˝ male NPT.
Mounting Orientation: Can be mounted in any position.
Weight: 3 oz (0.085 kg).
Specific Gravity: No minimum.

INSTALLATION

1.

Carefully unpack switch and remove any packing material
from unit. Prism surface must be clean for proper operation.

2.

Level Switch may be installed in any position. NOTE: Do not
install near infrared light sources.

3.

Prism surface must be at least 2" from any reflective surfaces.

4.

Apply thread tape or sealant to 1/2" male NPT thread. To
prevent damage to threads, avoid overtightening. NOTE:
Sealant must not come in contact with prism surface.

5.

Connect (+) 10-28 VDC power to red lead; return (-) to black
lead. CAUTION: Do not connect output to supply.

6.

Inspect and clean lens at regular intervals. Level switch not
recommended for use with liquids that leave deposits.

Model OLS Optical Level Switch

Specifications - Installation and Operating Instructions

Bulletin E-46

W.E. ANDERSON DIV., DWYER INSTRUMENTS, INC.

P.O. BOX 358 • MICHIGAN CITY, INDIANA 46361 U.S.A.

Phone: 219/879-8000

www.dwyer-inst.com

Fax: 219/872-9057

e-mail: [email protected]

Model No.
Model OLS-10
Model OLS-11
Model OLS-12

Wetted Materials

316 SS/Polysulfone

Polysulfone

PFA

OLS-10

1/2 NPT

1-3/4

[44.45]

1/16

[1.59]

15/64

[5.95]

7/8 HEX

[22.23 HEX]

HIGH

LOW

RED,
BLK, GNO
WHT, CONTROL

OLS-11

OLS-12

E-46 11/8/07 10:53 AM Page 1

Advertising