Dwyer WTP User Manual

Dwyer instruments, inc, Series wtp wireless temperature sensors

Advertising
background image

DWYER INSTRUMENTS, INC.

Phone: 219/879-8000

www.dwyer-inst.com

P.O. BOX 373 • MICHIGAN CITY, INDIANA 46361, U.S.A.

Fax: 219/872-9057 e-mail: [email protected]

The Series WTP Wireless Temperature Sensors can be quickly
installed on chilled water lines, air ducts or outside a building without
having to run additional wiring. By sampling the temperature
measurement every 10 seconds, the 3.6 V lithium battery is able to
power the unit for up to 8 years.

A reliable 418 MHz signal can carry the measurements up to 100 feet
without a repeater. With the optional 900 MHz repeater, measurements
can be transmitted up to 1000 feet away.

SPECIFICATIONS
Temperature Range:
-40 to 185°F (-40 to 85°C).
Accuracy: ±0.3°C.
Temperature Limits: 32 to 140°F (0 to 60°C).
Humidity Limits: 5 to 95% RH non-condensing.
Power Requirements: 2 AA 3.6V lithium batteries.
Transmitter Interval: Approximately 10 seconds.
Housing Material: ABS plastic.
Enclosure Rating: UL 94 V-0, NEMA 4X.
Antenna: 418 MHz - Built inside enclosure.
Weight: Duct/OSA: 1.25 lb (566 g); Immersion: 0.8 lb (363 g).
FCC Approval: FCC ID# T4F06811RH.
Agency Approvals: RoHS.

Series WTP Wireless Temperature Sensors

Specifications - Installation and Operating Instructions

Bulletin W-WTP

5 [127.00]

2-1/2

[63.50]

1/2˝ NPT CONDUIT
KNOCKOUT

3X 1/2˝ NPT

1/4

[6.35]

L

4-5/32

[105.41]

5

[127.00]

2-1/2

[63.50]

1/2˝ NPT
CONDUIT
KNOCKOUT

3X
1/2˝ NPT

5-3/4

[145.80]

1/2˝ NPT CONDUIT

KNOCKOUT

2-1/2

[63.50]

3X 1/2˝ NPT

FOR 1/2˝ NPT CONNECTION

1/4

[6.35]

L

4-5/32

[105.41]

DUCT MODEL

OSA MODEL

IMMERSION MODEL

When inserting batteries, observe polarity
markings inside unit for proper operation.

It is best to train output modules before mounting
the transmitters.

NOTICE

NOTICE

W-WTP:E-53(english) 12/23/09 8:35 AM Page 1