Model LVT1 Digital programmable Indoor

Thermostat with Heat Pump

111213

Installation, Mounting:



Caution: Turn off model LVT1 and the electronic devices (e.g.
heater, cooler) which will be connected, and the electric
source before installation and maintenance. It is highly
recommended that the installation procedure is processed by
trained professional.


1. Installation location:
The Thermostat is restricted to be used indoors only. It should
be mounted on an inner wall about 1.5m above the floor at a
position where it is readily affected by changes of the general
room temperature with freely circulating air. Avoid mounting
above or near hot surfaces or equipment (e.g. TV, heater,
refrigerator). Avoid mounting where it will be exposed to
direct sunshine, drafts, or in a laundry room or other enclosed
space. Do not expose this unit to dripping or splashing.

2. Wiring:
- Be sure main switch is at the middle (OFF) position, and

fan switch is at the (FAN AUTO) position.

- Wire the proper cables at the terminal block according to

the circuit diagram.

- Afterward, push all cables back into the wall.
- Do not use metal conduit or cable provided with a metal

sheath.

- It is recommended to add fuse or protective device in the

line circuit.


3. Mounting:
Using the accessory screws and wall anchors provided, mount
the thermostat with the key-hole at the back. The thermostat
should be mounted on the wall as shown in Figure 1.

Figure 1

4. Electrical Interface:

Terminals

Symbol

Switched Side, 24 VAC

R

Reversing Valve (Cool)

O

Reversing Valve (Heat)

B

Fan

G

Heater Output

W

Cooler Output

Y

Unswitched Side,24 VAC

C

Wiring diagram for thermostat:





Wiring diagram for heat pump thermostat (Compressor):

















Feature list

Operates on 1 stage Heat and 1 stage Cool

2 programs (Mo-Fr, Sa-Su)

4 Separate time and temperature settings for each program

Heat and Cool set-points for each program

Low battery indicator

EEPROM stores heat and cool program settings

Temperature display in °F or °C

Temporary program override

Permanent program override

Short cycle protection

Adjustable filter usage counter

Adjustable energy usage counter

Adjustable temperature control span

LCD backlighting

Defrost function


User Interface


1. Slide switch select System Mode
OFF:

No Heating and Cooling will be activated at any temperature.

HEAT:

Heating will be activated when condition is met.
Changeover valve always stays at Heat side.

COOL:

Cooling will be activated when condition is met.
Changeover valve always stays at Cool side.

2. Push Buttons

Symbol

Description

Up

Down

PROG

Enter to Program & Permanent Override
mode, Release Temporary Override

TIME

Set time and date

TEMP

Read and Set temperature control options

USAGE

Read and Set System Usage time

RUN

Confirm and Return


3. Select Fan Mode
Use the Fan slide switch to select Fan mode.

FAN AUTO:
Fan turns on whenever Heating or Cooling is on.

(Depends on HE:ON / HG:OFF setting)
FAN ON:
Fan stays on all the time.

4. Jumpers
Remove the front plate, the jumpers are at the circuit board.
Reset the thermostat is required if the jumper is changed the
position.

1. Temperature unit selection (C/F)

Set temperature unit °F or °C. The program will be restore
to default setting, when the setting is changed.

2. HE-HG selection (HE/HG)

HE - fan auto control for electrical heat.
HG - fan auto control for gas heat.

3. Delay / No Delay Selection (D/ND)

Heater

Cooler

No delay

10 sec

4 mins

Delay

4 mins

4 mins

Choose the Delay option if compressor heat is connected.


Operation


Normal Mode

Time Setting

1. Press [TIME], day icon starts flashing. Use [▲] / [▼]

keys to set the day.

2. Press [TIME], hour digits start flashing. Use [▲] / [▼]

keys to set hour.

3. While hour digits are flashing, press [TEMP] key to toggle

between 12-hour and 24-hour time mode.

4. Press [TIME], minute digits start flashing. Use [▲] / [▼]

keys to set minute.

5. Press [RUN] to confirm time settings; Press [TIME] to loop

back to set minutes.



Programming

Below is the default program:

Event

Time

Heat

Cool

M

O

F

R

WAKE 6:00 AM

70 °F (21°C)

78 °F (26°C)

OUT

8:00 AM

62 °F (17°C)

85 °F (29.5°C)

BACK 6:00 PM

70 °F (21°C)

78 °F (26°C)

SLEEP 10:00 PM

62 °F (17°C)

82 °F (28°C)

S

A

S

U

WAKE 6:00 AM

70 °F (21°C)

78 °F (28°C)

OUT 10:00 AM

62 °F (17°C)

85 °F (29.5°C)

BACK 6:00 PM

70 °F (21°C)

78 °F (26°C)

SLEEP 11:00 PM

62 °F (17°C)

82 °F (28°C)

Cooler

Fan

Transformer

C

W

Y

G

B

O

R

24VAC

Heater

Compressor

Fan

Heat

Changeover

valve

Cool

Changeover

valve

Transformer

C

W

Y

G

B

O

R

24VAC