Figure 2-5, Figure 2-6, Figure 2-7 – Innotech Device Network Cabling User Manual

Page 20: Incorrect station ig02 comms connection, Correct station ig02 comms connection, Correct station ics / ig02 network connection, Figure 2-5: figure 2-6: figure 2-7

Advertising
background image

© Mass Electronics Pty Ltd 2007

Innotech Device Network Cabling Installation Instructions

Edition 3.0 dated 05.12.2013

Page 20

2-2.2 Control Stations (ICS) and DynaLite Gateway (IG02)

Control Stations and DynaLite Gateways connect to the Global network and do not connect to the Net

network. This will present a few variations in how these devices could be connected to the network.

It is important to ensure that the screen is kept continuous.

This style of connection applies to all globally connected devices.

The rules of application are similar to that of the HMI or Converter connections in the prior section.

You must ensure the global and net cable lengths are the same.

In this correct example you can see that the GLB comms screen is in ‘S1’ terminal only. If you were to

use the ‘S1’ and ‘S2’ terminals you would break the continuity of the GLB screen. This could cause a

potential difference between each side of the ICS / IG02 and possibly introduce network reliability

issues.

The ICS / IG02 must have the earth terminal or the 24V neutral, connected to earth where available.

This will provide the path for the soft earth.

S1

- S2

+

S1

- S2

+

Figure 2-5:  Incorrect Station IG02 Comms Connection

Figure 2-6:  Correct Station IG02 Comms Connection

Device

Figure 2-7:  Correct Station ICS / IG02 Network Connection

Device

ICS / IG02

Advertising