Specification – Noby UK Noby-220iR2 2-Zone User Manual

Page 18

Advertising
background image

Noby-220iiiiR2 Installation Manual

Page 18

Software Revision1-0

-

-

-

Specification

PSU & Battery

Value

Unit

Comment

Supply Voltage

230

VAC

+10% -6% 50Hz/60Hz

Max. Input Current

60

mA

Battery

12

V

SLA 12V; 1.2Ah or 1.3Ah

PSU Output Voltage

13.68

V

+/- 150mV (@ Imax.a)

PSU Absolute Max Current

200

mA

Fuses:

F1,F2 Sndr 1,2

F3 Battery +'ve

500

1.0

mA

F500mA - quick blow
T1.0A - slow blow

Imin

8

mA

Imax.a

25

mA

Imax.b

-

not specified

Rimax – Max.Battery Circuit Resistance

2.5

ohms

detection delay 60s<t<120s

Max Battery Current Draw

180

mA

with 230VAC disconnected

Standby Battery Current

10

mA

with 230VAC fault condition

Standby Battery Time

>88

hrs

see note below**

Battery Low Voltage Detection

11.0

V

detection delay 60s<t<120s

Battery Final Voltage – Auto Disconnect

10.5

V

detection delay 60s<t<120s

PSU Charger Fault Detection

Yes

detection delay 60s<t<120s

230VAC Mains Loss Detection

Yes

off delay=90s; on delay=10s

Detection Circuits

Value

Unit

Comment

No. of circuits (zones)

2

Max detector current /circuit

1mA

e.g. 10 detectors at 100uA /circuit

End-Of-Line Capacitor EOLC

10.0

uF

non-polarised

Head Removal Monitoring

Yes

requires schottky diode bases

O/C Fault Detection

Yes

Max Loop Resistance

400

ohms

S/C Fault Detection

<120

ohms

Fire Alarm Detection

120-1500

ohms

Sounder Circuits

Value

Unit

Comment

Max. Combined Ext. Sounder Current

150

mA

@ 12.0V sounder spec. rating

End-Of-Line Resistors (EOLR)

10

Kohms

Open Circuit Detection

>20

Kohms

Short Circuit Detection

<5

Kohms

Fire Alarm Relay

1.0

A

SPDT 1A/30V voltage free

Internal Panel Sounder

>85

dB

measured at 3.3m, open field

Internal Panel Fault Tone

>65

dB

** 1.2Ah battery derated to 0.8C 88hrs standby followed by 0.5hrs in alarm with 150mA sounder o/p load.