Electrical connections – ROTRONIC CF3-W-US User Manual

Page 3

Advertising
background image

Dokument
IMA 203

Rev
1

Page
3 (4)

Electrical connections

The power supply has to be connected to

and

.

is considered as system

ground. The same ground reference has to be used for the CF3-W-US unit and for the
DDC/signal receiver.

PLEASE NOTE! The same ground reference has to be
used for the

CF3-W-US

unit and for the control system!

Terminal

Function

Electrical data

Standard settings

Settings of

this sensor

Power (+)


Power

ground (-)

24 VAC/DC+

(+-20%), 2W

24 VAC/DC-





System voltage
reference

OUT(1)


OUT(2)

Analogue

output 1 (+)

Analogue

output 2 (+)

0-10 VDC


2,0…10,0 VDC or

4,0 … 20,0 mA

0,9…1,6 VDC or

1.5 to 2,5 mA

0 VDC or 0mA

0-2000 ppm CO

2



0-2000 ppm CO

2



Status = ERROR


Status = NOT
READY

Table I. Connections of the main terminal of

CF3-W-US

Figure 5 The CF3-W-US PCB seen from the front and the back. The OUT2 jumper is in the default
position (voltage)

~

+

~

+