Self-diagnostics, Maintenance, Electrical connections – ROTRONIC CF3-W-US-FLI User Manual

Page 3

Advertising
background image

Dokument
IMA 212

Rev
1

Page
3 (4)

Electrical connections

The power supply has to be connected to

+~

and

.

is considered as system

ground. The same ground reference has to be used for the CF3-W-US-Disp-FLI unit
and for the DDC/signal receiver.

PLEASE NOTE! The same ground reference has to be
used for the
CF3-W-US-Disp-FLI unit and for the control

system!

Terminal

Function

Electrical data

Remarks

+~


Power (+)


Power ground (-)

24 VAC/DC+ (+-20%),

2W

24 VAC/DC-




System voltage reference

OUT1


OUT2

Analogue output

1 (+)

Silences the

acoustic alarm

0-10 VDC

0-2000 ppm CO

2


A push on the push button
silences the acoustic alarm
for 30 minutes.

Table I. Connections of the main terminal of CF3-W-US-Disp-FLI

LED Colour

Electrical data

Remarks

Green

0VDC

10VDC



Lit between 0-800 ppm CO

2

Yellow

0VDC

10VDC



Lit between 800-1400 ppm CO

2

Red

0VDC

10VDC



Lit above 1400 ppm CO

2

. Buzzer sounds.

Table II. The LEDs

Self-diagnostics

The system contains complete self-diagnostic procedures that are executed
automatically when the sensor is in operation. Sensors with display show a wrench if
an error is found. The wrench is shown during the first seconds after power up and if
the measuring range is exceeded.

Maintenance

The CF3-W-US-Disp-FLI is basically maintenance free in normal environments
thanks to the built-in self-correcting ABC algorithm.

PLEASE NOTE! The sensor accuracy is defined at continuous operation (at
least 3 weeks after installation)

Electronic products should be disposed of via a suitable recycling centre.