Electrical connections – ROTRONIC CF5-D User Manual

Page 3

Advertising
background image

Dokument
IMA 207

Rev
2

Page
3 (4)

Electrical connections

The power supply has to be connected to

and

.

is considered as system

ground. If the analogue output is connected to a controller the same ground reference
has to be used for
the CF5-D unit and for the control system! Unless different
transformers are used, special precautions need to be taken.


PLEASE NOTE! The
CF5-D signal and power supply
grounds are common.

NOTE! The same ground reference has to be
used for the
CF5-D unit and for the control
system!


Connect the power after mounting. The analogue
output should be connected before measuring.

Connection

Terminal

Function

Electrical Data

Remarks

Power (+)


Power ground (-)

24 VAC/DC+ (+-20%), 3W


24 VAC/DC-


2W without output load
See note 1!

Out(1)




Out(2)

Analogue Output 1 (+)




Analogue Output 2 (+)

0-10 VDC or 0-20 mA,

2-10 VDC or 4-20 mA,


Same as Output 1


According to positions of
Out(1) and start point
jumpers.
See note 2!


According to positions of
Out(2) and start point
jumpers.
See note 2!


Note 1: The ground terminal is used as negative power supply DC input or AC phase
ground

(halfwave rectifier).


Note 2: CF5-D can deliver a voltage or a current loop for Out(1) / Out(2). To change
between voltage and current output mode the hardware jumpers are used. There is one
jumper for Out(1) and one for Out(2), so that one output can be a voltage output and the
other a current output. Both, voltage output and current outputs, can have start points 0 % (0-
10 VDC or 0-20mA) or 20% (2-10 VDC or 4-20mA). The same start point is used for both
outputs. See the user manual.

~

+

~

+