Default output range, Formulas for calculation of output values, Output configurations – ROTRONIC CF8-W-Disp-GH User Manual

Page 3

Advertising
background image

Dokument
UMA 146

Rev
1

Page
3 (7)

Terminal

Default

Output

Default Output

Range

Outputs of this

sensor

Output Range of

this sensor

Out(1)

0-10VDC

0-2000 ppm CO

2

0-10VDC

0-4 % CO

2

Out(2)

0-10VDC

0-50

o

C

Relay

Closed

Open

> 1000 ppm CO

2

< 900 ppm CO

2


> 2,0 % CO

2

< 1,9 % CO

2

Table I. Default output configurations for

CF8-W-Disp-GH

Formulas for calculation of output values


Configuration


Output Range


Formula for calculation


0-10 VDC


0-2000 ppm CO

2


0-50

o

C


CO

2

value = Volt/10*2000


Temperature value in

o

C = Volt/10*50


2-10 VDC


0-2000 ppm CO

2

0-50

o

C


CO

2

value = (Volt –2)/8*2000


Temperature value in

o

C = (Volt –2)/8*50


4-20 mA


0-2000 ppm CO

2


0-50

o

C


CO

2

value = (mA-4)*2000/16


Temperature value in

o

C = (mA-4)*50/16


a-b


c–d


Value = (reading-a)/(b-a)*(d-c)+c

a = lowest value of the configuration
b = highest value of the configuration
c = lowest value of the range
d = highest value of the range

Table II. Calculation of CO

2

value and temperature value for

CF8-W-Disp-GH


The red LED is lit when the relay output is closed.

Output Configurations


The sensors/controllers are supplied from the factory (unless otherwise ordered) with
0...10VDC linear outputs for Out(1) and Out(2) (see Table I). If other options are
needed for the application, the output jumpers have to be configured before the unit
is powered up. Each jumper selection is independent from the others, except for the
“Start point selection” jumper, which affects both, Out(1) and Out(2), linear outputs.