Electrical data – Setra System Model ASM User Manual

Page 3

Advertising
background image

3

The current flows into the +EXC terminal and returns back to the power sup-

ply through the -EXC terminal (See Diagram 1). Note: The +SIG Out and -SIG

Out terminals are not used. The power supply must be a DC voltage source

with a voltage range between 9 and 30 VDC measured between the + and

- terminals. The unit is calibrated at the factory with a 24 VDC loop supply

voltage.

3.4 Cable for Bayonet Connectors

For good EMC performance, shielded cable shall be used and grounded to

earth ground. Cable shall only be used within a building and not be longer

than 30 m (100 ft.).

Diagram 1

Electrical Data

Signal Output Ranges

0-5 VDC, 0-10 VDC (4-wire); 4-20mA (2-Wire)

Nominal Excitation

24 VDC

Excitation Range

9-30 VDC (5 VDC & 4-20mA output)

15-30 VDC (10 VDC Output)

Current Consumption

<23mA

Circuit Response Time

<10ms (Voltage Version),

<80ms (4-20mA Version)

Warm-up, Environmental

Within +/-0.02%FS after 15 min. Warm-up Time

Miswiring

Reverse Excitation Protection

4.0. CALIBRATION

The ASM transducer is factory calibrated and should require no field adjust-

ment if mounted in a vertical position. Whenever possible, any zero and/or

span offsets should be corrected by software adjustment in the user’s control

system. However, fine zero and span adjustments can be made through use

of Secure-Cal

TM

accessory (purchased separately) for calibration access. The

Model ASM transducer zero offset is trimmed in the vertical position (pressure

port pointing downward) prior to shipping from factory.

4.1 Zero/Span Adjustments with Secure-Cal

TM

To make secure zero and span adjustments, attach SecureCal

TM

accessory to

ASM pressure transducer. (See Diagram 2).

+

_

9 to 30 VDC

ASM

Current

Monitoring

Device