0 model 269 performance specifications – Setra System 269 User Manual

Page 3

Advertising
background image

269

Current

Monitoring

Device

13.5 to 30 VDC

+

_

4.5 Restoring Factory Calibration

To restore factory set calibration, turn unit off power and press cal button. Turn on the power while cal button is
depressed and release cal button.

5.0 MODEL 269 PERFORMANCE SPECIFICATIONS

Performance

Codes V E G

Accuracy Class (FS)

±0.25% FS ±0.50% FS ±1.0% FS

Non-Linearity

Terminal Point

±0.15% FS ±0.35% FS ±0.75% FS

BFSL

±0.10% FS ±0.25% FS ±0.55% FS

Hysteresis (Typical)

±0.05% FS ±0.05% FS ±0.10% FS

Non-Repeatability

±0.05% FS ±0.05% FS ±0.10% FS


Thermal Effects

Compensated Range °F

20 to +140

Zero Shift %FS/°F

0.01% 0.02% 0.03%

Span Shift %FS/°F

0.01% 0.02% 0.03%

Maximum Line Pressure

2 psi

Overpressure

±15 in. W.C.

Long-term Stability

0.5% FS/1 Yr

Position Effect

Range Zero Offset (%FS/G)

(Unit is factory calibrated at 0g effect

To 0.1 in. WC 2.50

in the vertical position, pressure

To 0.5 in. WC 1.00

ports pointing upward.)

To 1.0 in. WC 0.50

To 2.5 in. WC 0.22

To 5 in. WC 0.14

Electrical

Calibrated at factory with a 24 VDC loop supply and a 250 ohm load.

Zero output factory set to 4±.04 mA for unidirectional pressure ranges and 12±.04 mA for

bidirectional ranges in vertical position.

Span factory set to 16±.04 mA.

Current Circuit Diagram

Security Cal Key

Diagram 3

Cal Encoder

Cal Button

3

Diagram 1

Diagram 2