4.3 Current Output Zero Adjustment

While monitoring the current output, and with the pressure port open to atmosphere or with zero pressure applied,
the zero may be adjusted by turning the zero potentiometer screw. The factory setting is 4mA (±0.08mA). For
absolute pressure ranges, the zero should be adjusted with a full vacuum applied. For compound pressure ranges, the
zero should be adjusted with

the unit at atmospheric pressure and the output adjusted as noted in

Diagram 6 below.

Note: When it is not possible to vent input pressure for zero adjustment (ie., hazardous gases), zero may be adjusted by pulling
a vacuum and setting the unit to 4.0 mA (±0.08 mA). This method may result in a small zero setting error due to variations in
barometric pressure.


4.4 Current Output Span Adjustment

Span or full scale output adjustments should only be performed by using an accurate pressure standard (electronic
manometer, digital pressure gauge, etc.) with at least comparable accuracy to the 217 transducer (±0.25% FS). With
full range pressure applied to the pressure port, the span may be adjusted by turning the span potentiometer screw.
The span (full scale) output is factory set to within ±0.08mA.

5.0 MODEL 217 PERFORMANCE SPECIFICATIONS

Accuracy RSS

*

(at constant temperature.)

±0.25% FS

Non-Linearity, BFSL

±0.15% FS

Hysteresis

0.20% FS

Non-Repeatability

0.02% FS

*RSS of Non-Linearity, Non-Repeatability and Hysteresis.

Thermal Effects

Compensated Range °F(°C)

+15 to +150 (-9 to +65)

Zero Shift %FS/100°F (50°C)

±2.0 (±1.8)

Span Shift %FS/100°F (50°C)

±2.0 (±1.8)

Environmental

Temperature
Operating** °F(°C)

-40 to +185 (-40 to 85)

Storage °F(°C)

-40 to +185 (-40 to 85)

Current unit ordered with Option N1:

Operating** °F (°C)

-22 to +176 (-30 to +80)

Storage °F (°C)

-22 to +176 (-30 to +80)

**Operating temperature limits of the electronics only. Pressure media temperatures may be considerably higher or lower.



Diagram 5

NOMINAL “INSTALLED” OUTPUT AT ATMOSPHERIC PRESSURE

PSI COMPOUND

CURRENT

RANGE

OUTPUT (mA)

-14.7 to 25

9.92

-14.7 to 50

7.63

-14.7 to 100

6.05

-14.7 to 250

4.89

-14.7 to 500

4.46

-14.7 to 1000

4.23

-14.7 to 3000

4.08

BAR COMPOUND

CURRENT

RANGE

OUTPUT (mA)

-1 to 1.7

9.92

-1 to 3.4

7.63

-1 to 7

6.00

-1 to 17

4.88

-1 to 35

4.44

-1 to 70

4.22

-1 to 200

4.07

6