4.2 Electrical Termination
Wiring: 3-Wire, 0 to 5, 0 to 10, 1-5 VDC and Remote Zero

The Model 231 when configured for voltage output is a 3-wire circuit device with
three terminals available for wiring. The -Excitation and -Output are commoned
on the circuit.

The 231 can operate from 12-30 VDC (18-28 VAC) nominal output power supply.

Note: The Zero terminals, connected to digital output, provide a contact closure relay for automatic reset to zero pressure
by the monitoring system. CAUTION: ZERO input is for dry contact, do no apply voltage to ZERO Terminals

The optional remote zero is a normally open relay wired between COM and
REMOTE ZERO terminals. In order to initiate ZERO function the relay contact shall
be closed.

Figure 5

A

B

C

D

MS1

50 25 10

5

MS2 100 50 20 10
MS3 250 125 50 25

A B C D

RANGES

ZERO

OUTPUT

A

B

C

D

4-20 0-5 0-10 1-5

A B C D

BAR
A.REV
SLOW
BI-DIR
SWAP

PSI
NORM
FAST
UNI-DIR
NORM

+

-

+

EXC.

COM

OUT

DC/AC
Power Supply

Controller

+

+

Installation of the Model 231 is now complete.

Important: Prior to putting the unit into service, press the “Zero” button,
then use the “Range Selection Switch” to select a range. After selecting a
range, press the “Zero” button again. For instructions regarding operation
of the Model 231, please refer to Section 5, page 10.