3 pressure specifications – Setra System Model 3200 User Manual

Page 4

Advertising
background image

4

the installation: The product is installed outside; all or any part of the cable is

exposed to the outside; the cable is greater than 30 meters in length. In order to

meet the Surge Immunity requirements, the following conditions must be fol-

lowed during installation:

1. Shielded cable must be used, and the shield must be tied to earth ground (not power supply

ground) on at least one end of the cable shield/drain wire. The shield must be maintained
all the way from sensor to the power supply.

2.

If unshielded cable is used, an earth grounded metal conduit fitting can be used to

replace the shielded cable.

3. For a sensor with a metal body or enclosure, the body/enclosure must be grounded to

earth. If a protective metal housing is used, the metal housing should be grounded to earth

4. If a protective plastic housing is used, the housing must be able to withstand at least
2 KV from the housing to earth ground, without damaging the circuit.

2.3 Pressure Specifications

Application pressure should be restricted to the rated-range of the transducer. The maximum

overpressure is the pressure limit at which the transducer will not show significant offset shift. The

minimum burst pressure is the test-rating for fluid containment
The data in the tables is "times rate ranges" (xRR).

All heavy duty pressure transducers are fitted with a restricting orifice by default.

x1.4

x3.0

x2.0

Rated psi

150 230 300 500 1000 1500 2300 3600 6000 10000 15000 25000

Range bar

10

16

20

35

70 100 160 250 400 700 1000 1600

Max. Over

Pressure (<)
Min. Burst (>)

x40

x20

x10

>4000 bar

x3.0

x2.5

3100 Standard Duty

3200 Heavy Duty

Rated psi

150 230 300 500 1000 1500 2300 3600 6000 10000 15000 25000 32000

Range

bar

10 16 20 35 70 100 160 250 400 700 1000 1600 2200

Max. Over

Pressure (<)
Min. Burst (>)

x40

x20

x10

>4000 bar