Sterlco Micro Series Water Temperature Control Unit User Manual

Page 33

Advertising
background image

3200 Series

ACS 3216 Operators Manual 33

CONTROLLER STATUS

POLL:

31 44

SELECT:

N/A

FORMAT:

Status

UNITS:

None

DESCRIPTION:

Instrument status.

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

N/A

N/A

Manual Control

Low Alarm 1

High Alarm 1

N/A

N/A

Open TC Alarm

N/A

Shorted TC Alarm

N/A

N/A

N/A

N/A

N/A

Process

Out

of

Cont.

PROCESSING

BIT#:

0

DESCRIPTION:

This status bit states whether this unit is currently processing.

0 = not currently processing (3200 manual mode)

1 = processing (3200 auto mode)

MANUAL CONTROL

BIT#:

2

DESCRIPTION:

Indicates if the control is in manual (open loop) or automatic (closed loop) control.

0 = Automatic Control

1 = Manual Control (or standby)

LOW ALARM 1

BIT#

3

DESCRIPTION:

Indicates that the first configured 3200 alarm is active. For example if Alarm 1 is not configured and Alarm 2
is set to be an absolute low alarm, this bit will be set if the temperature is lower than alarm setpoint 2.

HIGH ALARM 2

BIT#

4