Sterlco GC Series Central Chiller User Manual

Page 57

Advertising
background image

GC Series Central Chillers

Chapter 7: Appendix

57 of 79

40 TON (GCRC-140)

PERFORMANCE (NOMINAL DESIGN CONDITIONS)

COOLING CAPACITY

40

TONS

ALTITUDE

SEA LEVEL

COOLANT SUPPLY
TEMPERATURE

50

°F

COMPRESSOR POWER

38153

WATTS

AMBIENT AIR TEMPERATURE

95

°F

EER

12.58 BTU/WATT

COOLANT

WATER

COOLANT FLOW

96

GPM

SOUND POWER LEVEL

98

dBA

UNIT PRESSURE DROP

7

PSID

SOUND PRESS LEVEL @ 1
METER

dBA

OPERATING PARAMETERS

COOLANT SUPPLY
TEMPERATURE

20-80

°F

COOLANT FLOW

48-192

GPM

AMBIENT AIR TEMPERATURE

60-115

°F

MINIMUM LOAD

8.00

TONS

SPECIFICATIONS

COMPRESSOR

SCROLL

FRAME

GALVANIZED STEEL

EVAPORATOR

BRAZED PLATE

COOLANT CIRCUIT

NON-FERROUS

EVAPORATOR FILTER

20 MESH

WEIGHT (OPERATING)

2236

LBS

POWER

460V/3PH/60HZ

WEIGHT (SHIPPING)

1070

LBS

CONTROL CIRCUIT

24/120

VAC

ELECTRICAL ENCLOSURE

NEMA 4/12

COMPRESSOR RATED LOAD
AMPS

(2) @ 30.4 AMPS EACH

CONTROL

MICROPROCESSOR

40 TON (GCRC-140)

SPECIFICATIONS

AMBIENT TEMPERATURE
RANGE

-20 to 115

°F

SOUND POWER LEVEL

98

dBA

CONDENSER AIR FLOW

38061

CFM

SOUND PRESS LEVEL @ 1
METER

dBA

CONDENSER

ALUMINUM

FRAME

GALVANIZED STEEL

CONDENSER FANS

(3) 32 INCH AXIAL

PANELS

POWDER COATED
STEEL

CONDENSER FAN MOTOR

(3) 2 HP OAO, 1140 RPM, 3.4
FLA

WEIGHT (SHIPPING)

927

LBS

POWER

460V/3PH/60HZ

Advertising