Technical data, Service address/hotline – Timeguard TR 622 top2 User Manual

Page 14

Advertising
background image

Technical data

• Nominal voltage: 230–240 V~, +10 %/-15 %
• Frequency:

50-60 Hz

• Power consumption: max. 6 VA
• Switching output: phase-independent

(zero-crossover switching),

• TR 611 top2:

suitable for switching SELV
(Safe Extra-Low Voltage)

• Contact:

two way switch

• Contact material: AgSnO

2

• Switching capacity max.: 16 A, 250 V~, cos ϕ = 1;

10 A, 250 V~, cos ϕ = 0.6

• Switching capacity min.: 10 mA/230 V AC

100 mA/24 V AC/DC

• Incandescent lamp load:

2600 W

• Halogen lamp load:

2600 W

• Fluorescent lamp load: uncorrected:

1000 VA series corrected
730 VA (80 μF) parallel corrected

• Compact fluorescent lamps: 22 x 7 W, 18 x 11 W

16 x 16 W, 20 x 14 W, 23 x 15 W,

• Permissible ambient temperature: –30 °C ... +55 °C

• Protection class: II in accordance with

EN 60730-1 for designated installation

• Protection rating: IP 20 in accordance with

EN 60529

• Pollution level:

2

• Power consumption: 10 years at 20 °C

Service address/Hotline

Service address

Theben AG
Hohenbergstr. 32
72401 Haigerloch
GERMANY
Phone +49 (0) 74 74/6 92-0
Fax: +49 (0) 74 74/6 92-150

Hotline

Phone+49 (0) 74 74/6 92-369
Fax: +49 (0) 74 74/6 92-207
[email protected]
Addresses, telephone numbers etc.
www.theben.de

14