Timeguard DSS User Manual

Page 5

Advertising
background image

4

5

If only one DSS is required then connect the mains supply live (L) to
LIN on the DSS and leave the SLAVE connection formerly going to the
second DSS open circuit.
Further DSS’s can be added by copying the circuit connections
shown in Fig 3 between the two DSS’s. The LIN of the second DSS
is connected to LMASTER of the third and LIN of the third to
L (mains supply live) and so on for further DSS’s.

3. Commissioning.

Press the push button and the light(s) under control should come ON
for approximately 10 seconds. During this time the neon behind the
push button switches OFF. If the lamps under control are fluorescent
they will not switch ON immediately and the light intensity may be
reduced initially. If there are DSS’s installed as well repeat this test at
each switch.
Having established that the DS1 and any DSS’s are working correctly
the mains supply should be turned OFF and the two fixing screws
removed from the unit. The DS1 can then be pulled away from the
wall to enable access to the delay time adjuster (see fig 2a). The delay
time can then be set to the required level and the DS1 fixed to the wall
using the two fixing screws. The push-in screw covers can now
be fitted if required.
The mains supply should be turned ON and the push button pressed
to ensure the delay time is correct.

4. Operation.

Whenever light is required press the closest push button and the
light(s) under control will remain ON for the set delay time.

5. Replacing 2 Way and

Intermediate Switches.

This involves wire identification and tracing. Switch installation should
be left to a competent electrician who will be able to relate the circuit
diagrams shown in figs 4 to 11 to the practical installation.

Advertising
This manual is related to the following products:

DS2, DS1