Warning, Caution – TOHO ELECTRONICS TTM-10L User Manual

Page 2

Advertising
background image

4.2

TERMINAL CONNECTION DRAWING

4.3

CAUTION FOR WIRING CONNECTION

Wiring material with resistance less than 5

per wire should be used to connect R.T.D. with this unit.

Ω

The Specified extension lead wire or the wire itself should be used to connect thermocouple with this unit as wiring material.

In case this unit should be used close to the noise generators, please use shield-wires.

Please do not wire the Input/Output lines inside of the same duct and the pipes of electric wires.
The signal wire of Input/Output should be away from power supply and loaded lines at least 50cm.

For prevention of electric shock, please do wiring connection only after turning off Power.

WARNING

This unit does not function for approx. 4 seconds after turning on Power. (No function at Output side)

CAUTION

For prevention of

, please make sure to confirm the name labels i.e. Input terminal

mis wiring

Power source terminal

beside the each wire.

and

etc.

OPERATE FLOW AND PARAMETER INFORMATION

5.

5.1

METHOD TO CHANGE EACH DISPLAY

Power ON

Display type of Input/Output for confirmation

Press Mode Key more than 2 seconds

Mode Display

Parameter Display

Press Mode Key more than 2 seconds

5.2

OPERATE FLOW

shows the existence of Option, or it may not be displayed by the other parameter.

MODE DISPLAY

A

B

C

D

E

Return







Output

to A.

Process Variable

Setting Value

Alarm

Alarm Output

AT Start

Low Limit

High Limit Setting

Display

Setting

PARAMETER DISPLAY
・For PID Control(10.Kind of Control””or””)

1

2

3

4

7







D

Input/Output

Proportional Band

Integral Time

erivative Time

Proportional Cycle

Kind of

・For ON/OFF Control(10.Kind of Control””or””)

5

6

OFF Point Position

Sensitivity

8

9

10

11

12





SV Limiter Low

SV Limiter High

Kind of Control

PV Correction Value

Manual Reset

13

14

15

16

17







℃ ゚

Kind of Communication

Alarm Output Function Alarm Output Sensitivity

Decimal Position

Select

/ F

18

19

20

21

22

Return







Communication

Communication

Communication

Response

to 1 or 5.

Lock Display

Parameter

Speed

Address

Delay Time

12

12

12

12

① ② ③ ④ ⑤ ⑥ ⑦ ⑧ ⑨ ⑩ ⑪ ⑫

POWER

POWER

POWER

POWER

SUPPLY

SUPPLY

SUPPLY

SUPPLY

Alarm

Alarm

Alarm

Alarm

Output

Output

Output

Output

SSR

SSR

SSR

SSR

Drive

Drive

Drive

Drive

Output

Output

Output

Output

Communication

Communication

Communication

Communication

Thermocouple

Thermocouple

Thermocouple

Thermocouple

R.T.D.

R.T.D.

R.T.D.

R.T.D.

Current

Current

Current

Current

RS-485

RS-485

RS-485

RS-485

RS-232C

RS-232C

RS-232C

RS-232C

(A)

(A)

(A)

(A) (B)

(B)

(B)

(B)

S.G

S.G

S.G

S.G

(T)

(T)

(T)

(T)

(R)

(R)

(R)

(R)

Relay

Relay

Relay

Relay

Contact

Contact

Contact

Contact

Output

Output

Output

Output

12VDC/

12VDC/

12VDC/

12VDC/

24VDC

24VDC

24VDC

24VDC

Advertising