Electrical specifications – Trimec ES6000 Hook Lock User Manual

Page 2

Advertising
background image

Page 2

Page 3

Solenoid Leads Colour

Red

Black

Supply Voltage

12-30 VDC

Ground (0 V)

CAUTION!

Incorrect supply voltage may cause damage not covered by warranty. Please check supply voltage with a suitable meter

to ensure it is within 12-30 VDC.

This product has been designed for use in weather protected areas only. DO NOT OIL OR LUBRICATE.

6000 Series Microswitch Monitoring

The 6000 Series hook lock is fi tted with a UL approved changeover microswitch (max. rating: 125 VAC, 3 A / 60 VDC, 200 mA) to monitor
the lock and door status. The wiring diagram for the monitoring schematic is shown in Fig. 9 and on the back of the strike.

Certifi cation

AS4145.2 compliant

BS5872 approved

CE compliant

up to 4-hours fi re rating, depending on type of doorset
(in accordance with AS1905.1 - 1997, Part 1: Fire-resistant Doorsets)

Standard UL 1034 Tested for:

1,500 lbs. (680 kg) static strength rating

70 foot-lbs. dynamic strength rating

250,000 cycles endurance rating

At the request of ASSA ABLOY Australia, this model was tested to the following VOLUNTARY ratings:

2,000,000 cycles of operation

660 lbs. (300 kg) pre-load capability

4

Hour

Performance

Circuit Protection : Reverse Polarity and Back EMF protection. Solenoid is continuously rated.

A

Mark Lines

Door Frame

Extend

B

Extend

A

1/2 Door Thickness

Door Frame

Fig. 5 - Mark Horizontal Line on Door

Fig. 6 - Transfer Lines to Door Frame

Fig. 7 - Mark Parallel Lines

Fig. 8 - Mark Cutout and Route Opening

≥ 150mm

≥ 150mm

A

Door

TOP

BOTTOM

Cutout Dimensions

52

46

259

211

54.5

3.0

52

32

10

258.5

238.5

Current Draw

@ 12 VDC

Initially 830 mA reducing to 250 mA after 1 second

@ 24 VDC

Initially 530 mA reducing to 140 mA after 1 second

ELECTRICAL SPECIFICATIONS

N.C. (Normally Closed)

Common

N.O. (Normally Open)

Yellow

Violet

Brown

Door Monitor

Common

N.O. (Normally Open)

White

Orange

Grey

Lock Monitor

N.C. (Normally Closed)

Fig. 9 - Monitoring Schematic

Fig. 9 - Monitoring Schematic

Place roller striker at a desired position along the edge of the door. Measure half the height of the roller striker and mark a horizontal line
(A) on the side of the door (see Fig. 5). Note that the striker must NOT be placed within 150mm from the top or bottom of the door.

Remove striker, then close door and transfer horizontal line (A) to the door frame. Also, mark a vertical line on door frame
corresponding to one face of the door (see Fig. 6).

Open door, then mark on both the door and frame 2 lines (B) that are parallel to the vertical line, at a distance equal to half the thickness
of the door (see Fig. 7).

Extend lines A and B on the door and frame until they intersect. The 2 lines on the door frame are the centrelines of the cutout.

Measure and mark the cutout onto the door frame, then route out opening (see Fig. 8).

Using the wiring diagram provided on lock body or the datasheet, ensure all wiring is correctly connected and not rubbing on sharp edges.

Install hook lock into door frame cavity and secure with mounting screws provided.

Mortise roller striker into door if necessary, using the striker body as template. Secure striker to door, ensuring that the striker fi xing holes
are in line with the marked vertical centreline, and in the orientation as per Fig. 2.

Gently close door to check for correct alignment of striker when it engages the lock. A maximum of 1mm “door rattle” should be allowed.

Open and close door repeatedly to check for correct operation of all functions.

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

Mortise Installation