UEi Test Instruments UTL260 User Manual

Page 6

Advertising
background image

Audible Continuity

Open circuit voltage: less than 700mV
Overload protection: 250V DC or 250V AC rms

Measurement Specifications
*Alignment marks

Position the conductor within the jaws at the intersection of the
indicated marks as much as possible in order to meet this meter’s
accuracy specifications.

If the conductor is positioned elsewhere within the jaws, the max.
additional error resulted is 1.5%.

*Accuracy: ±(% of reading + number of digits) at 64˚ to 82˚F (18˚ to
28˚C) with relative humidity to 80%.

AC Current

Frequency response: 50/60Hz

DC Voltage

Input impedance: 10MΩ
Maximum input voltage: 600V DC or 600V AC rms

AC Voltage

Input impedance: 10MΩ
Frequency response: 40~400Hz
Maximum input voltage: 600V DC or 600V AC rms

Resistance

Open circuit voltage: less than 700mV
Overload protection: 250V DC or 250V AC rms

UTL260-MAN

P. 5

Range

Resolution

Accuracy

2A

0.001A

20A

0.01A

±(2%+5)

200A

0.1A

Range

Resolution

Accuracy

600V

1V

±(1%+5)

Range

Resolution

Accuracy

600V

1V

±(1.5%+5)

Range

Continuity beeper

< approximately 50Ω

Range

Resolution

Accuracy

2kΩ

±(1%+5)

MARK

CONDUCTOR

MARK

MARK