Maintenance:

Maintenance typically consists of an annual replacement of
the ultraviolet lamps.
UV lamps undergo a photochemical process during
operation. This slowly reduces the amount of UV light
generated to disinfect against airborne pathogens.

When installing new lamps, ensure that the lamp glass is
free from any fingerprints or debris, as this may alter the
path of the UV energy. Use rubbing alcohol and a dry cloth
to remove any surface contaminants.

Troubleshooting:

The Ultravation air disinfection equipment is designed to
provide many years of trouble free operation. In the unlikely
event of a problem, please contact your local dealer or
Ultravation directly. Before calling for service, you should
have your Model No; Serial No; Manufacturing Date;

• Verify the unit has power (120 volt)

• Power switch is in the ON position

• Lamps are securely plugged into their sockets

• The electronic circuit of a 2-lamp system only

operates when both lamps are operating.

• Verify fuses are not blown. Remove replaceable 5

amp MDL fuse from fuse holder and visually
inspect or perform a continuity test of the fuse.

• Verify what signal if any the UV Lamp Monitor LED

is emitting. (See below).

• Verify if in fact the UV lamps are on or off. Do not

look at the UV light without proper eye
protection.

Lamp Replacement:

*See Lamp Installation for Replacement Procedure.

NOTE:
When replacing lamps after 1 year or 2 years of
operation disconnect power to the unit first.
After the lamps are in place, complete steps 1-5 to set the
service indicator to 0.

For optimum 24/7 air stream disinfection it is
recommend the UV-C lamp is replaced on an annual
basis.