Ultravation UVS and UVE Remote Lamp - DC-IH-0214 User Manual

Page 2

Advertising
background image

2



















































Safety Precautions:

It is recommended that this unit be installed and
maintained by a trained technician:

WARNING: UV Hazard. Always protect eyes from
ultraviolet light. NEVER look at UV lamps in
operation. Unplug or disconnect power before re-
lamping or servicing.

WARNING: Severe eye damage or temporary
blinding may occur.

WARNING: DO NOT operate outside of Air Handler.
Mount lamp base to duct first.

WARNING: No openings in duct are allowed which
would give direct line-of-sight to the UV light.

In the event of accidental breakage or replacement of
the ultraviolet lamp, please ensure that the lamp is
disposed of in accordance with local and state
environmental laws regarding fluorescent lamps
containing mercury.

Notice:

All wiring inside of the duct or air handling system in
direct line of site of the UV lamp must be shielded with
aluminum foil tape or equivalent non-combustible
material. When installing this unit, select a mounting
location that prevents ultraviolet light exposure to
plastic flexible duct liner or other plastic components
with unknown resistance to ultraviolet light. Ultraviolet
light may cause color shift or structural degradation of
plastic HVAC components

Shipping and Packaging List:

• UVS or UVE Electrical Housing

• 6- ¾ inch 5/16 self tapping sheet metal screws

• Warning

Label

• Residential Warranty Card


UVS- 1200T, 1202T, 1900T, 1902T

• **1200T and 1900T Series- 1 12” or 17” T3

Lamp

• **1202T and 1902T Series- 2 12” or 17” T3

Lamp

• *8 or 12 T3 Lamp mounting plate mounting

screws

• *2 or 4 T3 Lamp mounting screws

• *1 or 2 T3 Lamp mounting plate

UVE- 1200T, 1202T, 1900T, 1902T

• **1200T and 1900T Series- One 12” or 17” T3

Lamp

• **1202T and 1902T Series- Two 12” or 17” T3

Lamp

• *1 or 2 T3 Lamp mounting plate w/ mounting

Hardware

UVE- 1224T, 12242T, 1924T, 19242T

• **1224T and 1924T Series- One 12” or 17” T3

Lamp

• **12242T and 19242T Series- Two 12” or 17”

T3 Lamp

• *1 or 2 T3 Lamp mounting plate w/ mounting

Hardware

• *1 or 2 T3 Lamp mounting bracket assembly

* Number depends on 1 or 2 T3 Lamps
** T3 Lamp gasket included